VEGA VEGASON 71 - 2 … 75 - 2 User Manual
Page 32

Measurement, Relay output
32
71 - 2 … 75 - 2
Mode
(Module 1, relay output 1) continuation
Mode 0 - 44 = 1
two-point level switch
switching command 1 via
switching command 2
correspond to function B
(protection against dry
running of pumps)
Switching command 1 and 2
(Module 1, relay output 1)
MODE 0 - 45 and 0 - 46
Mode 0 - 43 defines the measurement units
coordinated to the relay output.
Mode 0-44 determines the function of the relay
output.
Mode 0-45 = switching command 1 corresponds
relay switched on (on)
Mode 0-46 = switching command 2 corresponds
relay switched off (off)
With the operating sequence of the switching
commands, the A- or B-function i.e. overfill protec-
tion or protection against dry running of pumps is
determined.
See page 31 and 32.
The min.
∆
for the switching commands is 10 cm or
0,5 %.
Programming example for relay output 1 ...............
-
coordination to channel 1 with units in %
-
mode 1
-
two-point level switch in function A
(see page 31)
Coordination (channel 1 in %) ..................................
• select mode 0 - 43 in MODEFIELD
• program figure 2 in PARAMETER FIELD
• then store with STO-button
Mode (two-point level switch) ....................................
• select mode 0 - 44 in MODEFIELD
• program figure 1 in PARAMETER FIELD
• then store with STO-button
Switching command 1 (on) ......................................
• select mode 0 - 45 in MODEFIELD
• program 025.0 % in PARAMETER FIELD
• then store with STO-button
Switching command 2 (off) .......................................
• select mode 0 - 46 in MODEFIELD
• program 050.0 % in PARAMETER FIELD
• then store with STO-button
Same function and procedure
for module 1, relay output 2
and module 2, relay output 3 and 4, however
with respective modes, see page 31.
0
25
75
100
50
% m
distance acc. to sensor type
switching command 1,
Mode 0-45
switching command 2,
Mode 0-46
(off)
(on)