Adjustment at level measurement

71 - 2 … 75 - 2

21

Empty / full adjustment in m without product level change

Programming pre-requirement
Mode 10 = 1
Mode 40 = 11

With this adjustment procedure two distances
(sensor … product surface) are defined in m
relating to the levels of 0 % and 100 %.

MODE 0 - 11 and 0 - 12

Programming example

with VEGASON 73 - 2

(individual programming sequence of the empty /
full adjustment)

• select mode 0 - 12 in MODEFIELD
• program 01.00 m in PARAMETER FIELD
• then store with STO-button

• select mode 0 - 11 in MODEFIELD
• program 09.00 m in PARAMETER FIELD
• then store with STO-button

Empty / full adjustment in % with product level change

Programming pre-requirement
Mode 10 = 3
Mode 40 = 11

MODE 0 - 11 and 0 - 12

Programming example

with VEGASON 73 - 2

(individual programming sequence of the empty /
full adjustment)

• select mode 0 - 12 in MODEFIELD
• program 075.0 % in PARAMETER FIELD
• then store with STO-button

• select mode 0 - 11 in MODEFIELD
• program 025.0 % in PARAMETER FIELD
• then store with STO-button

With this adjustment procedure two levels are
defined in % relating to two different, actually
measured distances (sensor … product surface).

The difference should be as large as possible. The
central electronics determines the adjusted range
(e.g. 25 … 75 %) from the total range (0 … 100 %).

Same procedure for channel 2, however
mode 0 - 21 and 0 - 22.

1

distance

9

100

m
0

%

0

25

50

75

5

7

3

1 m distance

^ 100 %

9 m distance

^ 0 %

1

9

100

0

25

50

75

5

7

3

measured

distance

^ 75 %

measured

distance

^ 25 %

m
0

%

level

distance level