Hart, Menu schematic, Setup – VEGA VEGABAR 40 HART User Manual

Page 32

background image

32

VEGABAR 40 (HART

®

)

Setup

HART

®

menu schematic

A

Hart Communicator

Self Test

in Progress

Firmware Rev: F2.2
Module Rev: 3.6

01992-96 FRSI

Generic: SENSOR
PV

80.945 mbar

HELP

EXIT

Generic: SENSOR
Device setup

1 Process variables
2 Diag/Service
3 Basic setup
4 Detailed setup
5 Review

SAVE HOME

1

2

3

4

5

1.1

4.1
(5.1)

4.2
(5.2)

Generic: SENSOR
PV URV

100.000 mbar

90.300

mbar

HELP DEL

ESC ENTER

Generic: SENSOR
Process variables

1 Snsr

80.945 mbar

2 AI % rnge
3 AO1 mA

HELP SAVE

HOME

Less important
menu windows

Not required, unimportant
or blocked menu windows

Important and
required
menu windows

B

Switch on:

after approx.
20 s

Set up the sensor in the sequence of the
letters A, B, C and D (adjustment without
medium).
For the adjustment with medium you set
up the sensor in the sequence A1, B1, C
and D.

Generic: SENSOR
Online(Generic)

1 Device setup
2 PV

80.945 mbar

3 PV AO mA
4 PV LRV bar
5 PV URV bar

SAVE

Generic: SENSOR
AO1

16.952 mA

HELP

EXIT

Generic: SENSOR

1 PV

LRV bar

2 PV

URV bar

HELP

HOME

Generic: SENSOR

1 PV LRV bar
2 PV URV bar

HELP

HOME

Generic: SENSOR

1 PV

LRV bar

2 PV

URV bar

HELP SEND

HOME

Generic: SENSOR

– WARNING –

Pressing "OK“ will
change device output.

Put loop in manual.

ABORT OK

continue like under
A figure 4.1(5.1)

Generic: SENSOR

– WARNING –

Return control loop
to automatic control

OK

Generic: SENSOR

1 PV

LRV

bar

2 PV

URV

bar

HELP

HOME

Empty adjustment without
medium

Full adjust-
ment without
medium

Generic: SENSOR
PV LRV

0.000 mbar

10.000

mbar

HELP DEL

ESC

ENTER

continue like under 4