beautypg.com

Floating relay output (cap e30 r), Floating relay output (cap e31 r) – VEGA VEGACAP 82-98 User Manual

Page 23

background image

VEGACAP

23

-

+

1

2

3

4

5

~

~

-

+

1

2

3

4

5

~

~

-

+

Electrical connection

Control of alternating current loads

The transistor switches a galvanically sepa-
rated alternating voltage 10 … 42 V AC to a
load.

Floating relay output (CAP E30 R)

Relay output

Power supply

1

2

3

4

5

6

+

L1

-

N

7

8

Relay output

Power supply

Relay output

The transistor switches an alternating voltage
10 … 42 V AC, which is also supply voltage,
to a load.

Note

The transistor outputs of several VEGACAP
can be switched in series or in parallel to
connect the signals logically. The wiring must
be done so that terminal 2 has a higher volt-
age than terminal 3.

Voltage supply: 20 … 250 V AC,
50/60 Hz; 20 … 72 V DC (for further informa-
tion see technical data)

Is used to switch external voltage sources to
relays, contactors, magnet valves, signallers,
horns etc.

Floating relay output (CAP E31 R)

Voltage supply: 20 … 250 V AC,
50/60 Hz; 20 … 72 V DC (for further informa-
tion see technical data)

In conjunction with oscillator CAP E31 R, the
measuring probes VEGACAP 27, 35 and 98
are adjustment-free and suitable for adhesive
products.

With double relay (DPDT), i.e. both relays
carry out the same switching function, e.g.
simultaneous control of a horn and a magnet
valve.