beautypg.com

3 electrical connection, 1 connection instructions, 2 connection plan – VEGA VEGACAP 82-98 User Manual

Page 21

background image

VEGACAP

21

3.2 Connection plan

Non-contact switch (CAP E30 C)

1 2 3

AC

L1 N

Earth

DC

+

or
DC

+

Electrical connection

3 Electrical connection

3.1 Connection instructions

Danger

Switch off the power supply before starting
connection work.

The electrical connection must be carried out
in accordance with the integrated oscillator
version. Connect mains voltage acc. to the
following connection plans.

Note

Give attention when replacing the housing
cover that the inspection glass is above the
control lamp (LED).

Note

If strong electromagnetic interference is ex-
pected, we recommend the use of screened
cable. The screening of the cable should only
be earthed only on the sensor end (elec-
trode).

As a rule, connect VEGACAP with vessel
ground (PA). To do this, use the ground ter-
minal on the housing (VEGACAP 27, 35 and
98) or the thread on the hexagon surfaces of
the mounting boss (screw
M4 x 5). On VEGACAP 97 terminal 3 must be
connected. This connection is used to draw
the ground potential as well as to drain off
electrostatic discharge.

1 Housing cover
2 Oscillator, e.g. CAP E30
3 Housing

1

2

3

Voltage supply: 20 … 250 V AC,
50/60 Hz; 20 … 250 V DC (for further infor-
mation see technical data)