Power-Sonic PSC-124000A User Manual
Page 5

5
power cord. Use a flat head screwdriver or a coin to pry open the fuse drawer or holder. Replace the
blown fuse with the spare You can use the old fuse to push out the spare fuse. Now is a good time to
install a new spare fuse. Replace fuses only with the same type (as indicated in this manual) and value
(as indicated on the charger).
CLEANING - Unplug the charger before attempting any cleaning. If it becomes necessary to clean the
enclosure, wipe the exterior of the enclosure with a damp cloth and a mild detergent. Do not use an
abrasive cleanser. Do not spray cleaners directly onto the charger or immerse unit in water.
BATTERY CHARGER SPECIFICATIONS
Operating temperature
0 to 35° C (32 to 95° F)
Storage temperature
-40 to 80° C (-40 to 176° F)
Dimensions
H 3.40” (8.6cm) x W 6.65” (16.9cm) x D 5.30” (13.5cm)
Weight
About 7.4lbs. (3.4kg)
Input fuse type
5x20mm fast acting, miniature glass fuse, UL & CSA approved.
Power Requirements
115/230 V~, 50-60 Hz, .98 A RMS
OUTPUT RATING @ 25° C
Charge Amps (lmax)
4A ± 2%
Charge Voltage Load With Battery 14.70 ± 0.30
Float Voltage Load with battery
13.58± 0.12
Switch Amps (lsw)
0.3A ± 5%
CHARGING BATTERIES
Our Technical Manual provides detailed information about charging procedure. A copy can be
downloaded from our website: www.power-sonic.com (go to Technical and click on the tab at the
right hand side of the page).