Power-Sonic PSX12-6.5s User Manual
Psx series, Vrla 6yr design life at 20 ) ºc

PSX Series
Designed for UPS Applications
Discharge Characteristics (25ºC, 77ºF)
Physical Specification
Internal Resistance mΩ
Dimensions (mm)
Standard terminal (mm)
PSX12-6.5S 12V 6.5AH
Nominal Voltage
Nominal Capacity (20HR)
12V
6.5 AH
Dimension
Length
Width
Container Height
Total Height (with terminal)
Weight
Standard Terminal
F1 (Neg.) F2 (Pos.)
Approx 2.10kg
151
51
92
98
2 mm
2 mm
2 mm
2 mm
+
-
+
-
+
+
-
Capacity
Affected by
Temperature
Standby
C
o
ns
ta
nt
V
ol
tage
C
har
ge
Recommended Charge
Current less than 1.85A
Voltage 13.5V ~
13.8V at 25°C (77°F)
40°C (104°F)
25°C (77°F)
0°C (32°F)
103%
100%
86%
Approx 35.0 mΩ
Power-Sonic Europe Limited
3 Buckingham Square, Wickford, Essex, SS11 8YQ
Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902
www.power-sonic.co.uk
Rev3 02/13
-
(VRLA 6yr Design Life at 20
)
ºC
92
2
98
2
+
-
151
2
26
2
51
2
Power
Rating
3hr to(1.67V/cell)
1hr to(1.67V/cell)
15min to(1.67V/cell)
20.46 Watts
49.50 Watts
151.92 Watts
4.75 / 6.35
6.35 / 7.95
3.2 / 3.4
0.8
F1 / F2
Constant Power Discharge Characteristics Unit: Watts / Cell (25ºC, 77ºF)
Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)
In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E
F.V(V/cell)
15min
1H
3H
1.85
10.48
3.67
1.58
1.80
11.45
3.91
1.62
1.75
12.51
4.09
1.65
1.70
13.39
4.22
1.70
1.67
14.26
4.37
1.78
1.60
14.94
4.52
1.82
F.V(V/cell)
15min
1H
3H
1.85
19.50
7.07
3.10
1.80
21.15
7.50
3.16
1.75
22.80
7.81
3.21
1.70
24.06
8.03
3.29
1.67
25.32
8.25
3.41
1.60
26.19
8.50
3.50