beautypg.com

Power-Sonic PSX12-6.5 User Manual

Psx series, Vrla 6yr design life at 20 ) ºc

background image

PSX Series

Designed for UPS Applications

Discharge Characteristics (25ºC, 77ºF)

Physical Specification

Internal Resistance mΩ

Dimensions (mm)

Standard terminal (mm)

PSX12-6.5 12V 6.5AH

Nominal Voltage

Nominal Capacity

12V

6.5 AH

Dimension

Length

Width

Container Height

Total Height (with terminal)

Weight

Standard Terminal

F2

Approx 2.00kg

151

65

94

100

2 mm

2 mm

2 mm

2 mm

+

-

+

-

+

+

-

Capacity

Affected by

Temperature

Standby

Cons

tant

V

o

lta

ge

Charg

e

Recommended Charge
Current less than 1.62A
Voltage 13.5V ~
13.8V at 25°C (77°F)

40°C (104°F)

25°C (77°F)

0°C (32°F)

103%

100%

86%

Approx 20.0 mΩ

Power-Sonic Europe Limited

3 Buckingham Square, Wickford, Essex, SS11 8YQ

Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902

[email protected]

www.power-sonic.co.uk

Rev3 02/13

-

(VRLA 6yr Design Life at 20

)

ºC

94

2

100

2

+

-

151

2

43

2

65

2

Power

Rating

3hr to(1.67V/cell)

1hr to(1.67V/cell)

15min to(1.67V/cell)

19.92 Watts

49.74 Watts

133.86 Watts

6.35

7.95

3.4

0.8

F2

Constant Power Discharge Characteristics Unit: W atts / Cell (25ºC, 77ºF)

Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)

In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E

F.V(V/cell)

15min

1H

3H

1.85

9.20

3.72

1.46

1.80

10.09

3.93

1.58

1.75

11.06

4.11

1.64

1.70

11.83

4.25

1.69

1.67

12.51

4.38

1.73

1.60

13.19

4.54

1.78

F.V(V/cell)

15min

1H

3H

1.85

17.17

7.18

2.87

1.80

18.62

7.55

3.07

1.75

20.08

7.86

3.18

1.70

21.15

8.08

3.26

1.67

22.31

8.29

3.32

1.60

22.99

8.55

3.40

Table of contents