Power-Sonic PSX12-6.0 User Manual
Psx series, Vrla 6yr design life at 20°c)

PSX Series
Designed for UPS Applications
Discharge Characteristics (25ºC, 77ºF)
Physical Specification
Internal Resistance mΩ
Dimensions (mm)
Standard terminal (mm)
PSX12-6 12V 6.0AH
Nominal Voltage
Nominal Capacity
12V
6.0 AH
Dimension
Length
Width
Container Height
Total Height (with terminal)
Weight
Standard Terminal
F2
Approx 1.80kg
90
70
101
107
2 mm
2 mm
2 mm
2 mm
+
-
+
-
+
+
-
Capacity
Affected by
Temperature
Standby
Co
nst
a
n
t V
ol
tag
e
C
ha
rg
e
Recommended Charge
Current less than 1.5A
Voltage 13.5V ~
13.8V at 25°C (77°F)
40°C (104°F)
25°C (77°F)
0°C (32°F)
103%
100%
86%
6.35
7.95
3.4
0.8
F2
Approx 25.0 mΩ
Power-Sonic Europe Limited
3 Buckingham Square, Wickford, Essex, SS11 8YQ
Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902
www.power-sonic.co.uk
Rev3 - 02/13
-
(VRLA 6yr Design Life at 20°C)
-
+
90
2
72 2
101
2
107
2
70
2
Power
Rating
3hr Rate(1.67V/cell)
1hr Rate(1.67V/cell)
15min Rate(1.67V/cell)
18.24 Watts
43.32 Watts
122.22 Watts
Constant Power Discharge Characteristics Unit: Watts / Cell (25ºC, 77ºF)
Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)
In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E
F.V(V/cell)
15min
1H
3H
1.85
8.40
3.20
1.37
1.80
9.22
3.42
1.43
1.75
10.09
3.58
1.47
1.70
10.77
3.69
1.51
1.67
11.45
3.82
1.58
1.60
12.03
3.95
1.63
F.V(V/cell)
15min
1H
3H
1.85
15.71
6.18
2.68
1.80
16.98
6.56
2.78
1.75
18.33
6.84
2.85
1.70
19.30
7.03
2.92
1.67
20.37
7.22
3.04
1.60
21.05
7.43
3.11