Power-Sonic PSX12-130 User Manual
Psx series, Vrla 10yr design life at 20 ) ºc

PSX Series
Designed for UPS Applications
Discharge Characteristics (25ºC, 77ºF)
Physical Specification
Internal Resistance mΩ
Dimensions (mm)
Standard terminal (mm)
PSX12-130 12V 130AH
Nominal Voltage
Nominal Capacity
12V
130 AH
Dimension
Length
Width
Container Height
Height to top of terminal
Weight
Standard Terminal
T11
Approx 37.6kg
410
177
225
211
2 mm
2 mm
2 mm
2 mm
+
-
+
-
+
+
-
Capacity
Affected by
Temperature
Standby
Con
s
tant
V
ol
tage
Char
ge
Recommended Charge
Current less than 32.5A
Voltage 13.5V ~
13.8V at 25°C (77°F)
40°C (104°F)
25°C (77°F)
0°C (32°F)
103%
100%
86%
Approx 4.0 mΩ
Power-Sonic Europe Limited
3 Buckingham Square, Wickford, Essex, SS11 8YQ
Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902
www.power-sonic.co.uk
Rev3 02/13
-
(VRLA 10yr Design Life at 20
)
ºC
Power
Rating
3hr to(1.67V/cell)
1hr to(1.67V/cell)
15min to(1.67V/cell)
403.92 Watts
1035.96 Watts
2903.04 Watts
225
2
177
2
21
1
2
410
2
In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E
Constant Power Discharge Characteristics Unit: Watts / Cell (25ºC, 77ºF)
Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)
F.V(V/cell)
15min
1H
3H
1.85
192.55
77.60
30.26
1.80
219.32
81.87
31.91
1.75
239.49
85.65
32.50
1.70
255.69
88.37
33.47
1.67
271.89
91.37
34.92
1.60
290.81
94.58
35.89
F.V(V/cell)
15min
1H
3H
1.85
359.29
149.57
59.46
1.80
403.71
157.14
62.27
1.75
435.53
163.64
63.24
1.70
458.52
168.20
64.89
1.67
483.84
172.66
67.32
1.60
508.86
177.80
69.06
310
2
20
M8
6
Torque 11.0 -14.7 Nm
T11 Threaded Insert 8mm Stud