Schneider Electric XY2 CH User Manual
Page 7

5
WIRING (fig. 6)
1. Remove the cover from the device
by unscrewing the four screws .
2. Remove the cap
or unscrew the blanking plug depending on the desired point of entry.
3. Attach the cable gland (not supplied).
4. If required, re-attach the blanking plug
and its nut into the empty hole
(tightening torque = 1±0.1 Nm / 0.73±0.07 lb.ft).
5. Connect the electrical cables to the yoke screw terminals
. In case of pilot lights (not included), pass the
cables through the hole (fig.9), fix the pilot light and after that connect the cables to the yoke screw
terminals.
(tightening torque = 1±0.2 Nm / 0.73±0.15 lb.ft).
6. Check that there are no cables passing through the reset area
.
7. Mount the cover onto the device
using the four screws
(tightening torque = 1.5±0.1 Nm / 1.1±0.369 lb.ft).
8. Install a type gG 10A protective fuse for XY2CH 2 contacts.
Install a type gG 6A protective fuse for XY2CH 3 contacts.
MAINTENANCE, RESTARTING AND CHECKING
Once you have engaged the cable, inspect the installation along the full length of the cable to identify the
reason for the emergency stop order before resetting the XY2CH.
The XY2CH and its cable and accessories must be periodically checked depending on the outside pollution
level and the number of operations.
The reset push button must be replaced in accordance with the diagram (fig.7). Take into account the
plastic part behind the cover (fig.8).
The reset push button must be replaced with the same type of push button. Check that the retaining strip is
present and correctly oriented as shown on the diagram.
During scheduled maintenance operations, check:
• The tightening torque of the XY2CH screws and components and other accessories (cable clamp, cable
guide, etc.) at least once per year.
• The condition of the cable and other associated elements (cable clamp, cable guide, etc.). The cable
sheath may be worn, but this wear should not prevent the cable from moving freely within the accessories.
If the sheath is torn or contains holes, change the cable.
• The condition of the XY2CH bellows. There must be no holes, slits or cracks in the bellows. If the bellows
are damaged, replace the XY2CH.
RISK OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Switch off the power supply of the device.
• Use an IP65 cable gland.
• Protect the installation against power surges.
• Use appropriate personal protective equipment (PPE) and follow the relevant working instructions for
electrical environments. See NFPA 70E.
• Always use an appropriate electrical measuring device to confirm that the entire installation is powered
down.
Failure to follow these instructions will result in death or serious injury.
RISK OF UNINTENDED EQUIPMENT OPERATION
• Do not remove non-detachable components.
• Ensure that the reset switch zone remains empty.
• Check that none of the device components is deformed by an electrical cable once the cover is closed.
• Check that the cover is securely closed.
Failure to follow these instructions will result in death or serious injury.
RISK OF PHYSICAL INJURY
Always check the product functioning before restarting.
Failure to follow these instructions will result in death or serious injury.
DANGER
DANGER
DANGER
DANGER
DANGER
DANGER
schneider.fm Page 5 Friday, May 31, 2013 2:08 PM