beautypg.com

Maintenance – York FAN COIL YWC User Manual

Page 12

background image

MAINTENANCE

MOTOR

The blower motor should be cleaned annually and if it

has oiling ports, it should be oiled with a good grade of

SAE 20 oil. Normally a few drops of oil in each bearing

is sufficient.

If motor service

is

required,

it

can be removed

in the

following manner:
1. Disconnect electrical power to

the

unit at

the

discon-

nect switch and lock out.

2. Remove two screws, securing blower deck

to

unit.

3. Locate motor lead wires where they connect

to

the

side panel, (lower rear on the electrical box side).

4. The quick connect plug needs

to

be squeezed on top

and bottom to release

it

from

its

socket (dual motor

units

have two plugs).

5. Now slide blower

/

motor deck out of

unit to ser-

vice.

6. Reverse process to install.

COIL

The coil must be kept clean by any of the following

methods.
1. Cleaning with low-pressure compressed air.
2. Flushing or rinsing with water (a detergent is ad-

visable for greasy surfaces).

3. Prior to the water system start-up and balancing, the

chilled/hot water systems should be flushed to clean

out dirt and debris, which may have accumulated

during construction. All unit service valves are to

be closed during this process. Strainers are to be

installed in the piping mains to prevent this material

from entering the units during normal operation.

FILTERS

Clean or Replace Air Filters Regu-

larly

The intervals at which filters require replacement

depend on local conditions.

Because of dust and lint in the room, room-air filters load

up much more rapidly than outdoor-air filters. Under

normal conditions, the room air filter requires cleaning

every six to eight weeks.

The filter is a permanent type and may be removed and

washed with a garden hose. Filter should be completely

dry before reinstalling. To remove the filter, rotate the

retaining rod holding the front edge of the filter so it

can drop below the front panel of the cabinet, then pull

outward to remove. To reinstall the filter, slide the filter

into the filter channels on both sides of the unit. Rotate

filter retaining rod on lower front edge of cabinet door

so that it is under the filter, then push the rod upward

into the cabinet door.

To ensure proper maintenance of the filters, it is best

to follow an organized maintenance procedure. The

following one is recommended:
Divide the total number of units on the job into six

equal groups. Each week inspect, clean or replace the

filters in each group, in rotation. This insures a uniform

servicing interval. The interval may be lengthened or

shortened as determined by experience. If inspection

shows only the room-air filter to be dirty, this one alone

should be replaced.

Dirty filters reduce the air and heating

capacities of the Unit. When the filters

are excessively dirty, the unit heating

capacity will be so reduced that it is in-

effective for heating the room. When

a room fails to heat, always check the

filters.

CLEAN UNIT INTERIOR

Once a year clean the fans and coils of the unit

thoroughly. Remove the access panel as necessary.

Wipe the interior of the unit clean with a rag. Wipe the

motor and inside and outside of the fan housings. (In

cooling units, clean out the drain pan.)

Tele. 800-861-1001

www.York.com

P.O. Box 1592, York, Pennsylvania USA 17405-1592

Subject to change without notice. Printed in USA

Copyright © by Johnson Controls 2006

ALL RIGHTS RESERVED

Form 115.20-NOM3 (1006)
Supersedes: Form 115.20-NOM3 (105)

This manual is related to the following products: