343615-YTG-A-0807
Unitary Products Group
27
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION
TABLE 28: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
USED FOR
A
7/8” KO
1
1. Opening in the bottom to the unit can be located by the
side in the insulation.
Control Wiring
2
2. Do not remove the 2” knockout ring.
Side
Bottom
B
2” KO1
Power Wiring
Side
Bottom
C
1-5/8” KO
Gas Piping (Front)
D
1-1/2” KO
Gas Piping (Bottom)
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
CONTROL BOX
ACCESS
A,B
WIRING ENTRY
(See Detail “B”)
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
BLOWER MOTOR
ACCESS
FILTER
ACCESS
DOT PLUGS
TABLE 29: MINIMUM CLEARANCES
LOCATION
CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Rear
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
24”
Below Unit
1
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
0”
Above Unit
2
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
72” (For
Condenser Air Discharge)