17 dy048 cooling capacities (4 ton) – York DY 036 User Manual
Page 15
343615-YTG-A-0807
Unitary Products Group
15
TABLE 17: DY048 COOLING CAPACITIES (4 TON)
Air on Evap-
orator Coil
Temperature of Air on Condenser Coil
75°F
85°F
CFM
WB
(°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
1200
72 58
2.8
32
28
25
22
18
-
-
54
3.1
30
27
23
20
17
-
-
67 57
2.8
43
39
36
32
29
26
22
51
3.1
40
36
33
29
26
23
19
62 53
2.8
53
47
44
40
37
33
30
47
3.0
47
44
41
37
34
30
27
57 51
2.8
51
51
49
45
42
38
35
46
3.0
46
46
43
39
36
32
29
1400
72 58
2.8
34
30
26
22
18
-
-
55
3.1
33
29
25
21
17
-
-
67 56
2.8
45
41
37
33
29
25
21
52
3.1
43
39
35
31
27
23
19
62 53
2.8
53
50
46
41
37
33
29
48
3.0
48
46
43
39
35
31
27
57 51
2.8
51
51
51
47
43
39
34
46
3.0
46
46
45
41
37
33
29
1600
72 57
2.8
36
32
27
22
18
-
-
55
3.1
36
31
26
22
17
-
-
67 56
2.8
48
43
39
34
29
25
20
52
3.1
46
42
37
32
28
23
18
62 53
2.8
53
53
47
43
38
33
29
48
3.1
48
48
46
41
36
32
27
57 51
2.8
51
51
53
48
43
39
34
47
3.0
47
47
48
43
39
34
29
1800
72 57
2.8
39
33
28
23
17
-
-
55
3.1
38
33
28
22
17
-
-
67 56
2.8
52
46
40
35
30
24
19
52
3.1
49
44
39
34
28
23
18
62 53
2.8
53
53
50
45
39
34
29
48
3.1
48
48
47
41
36
31
25
57 51
2.8
51
51
52
46
41
36
30
47
3.1
47
47
47
42
37
31
26
2000
72 57
2.8
41
35
29
23
17
-
-
55
3.1
41
35
29
23
17
-
-
67 55
2.8
55
48
42
36
30
24
18
52
3.1
52
47
41
35
29
23
17
62 52
2.8
52
52
52
46
40
34
28
48
3.1
48
48
48
42
36
30
24
57 50
2.8
50
50
50
44
38
32
26
46
3.1
46
46
46
40
34
28
23
95°F
105°F
1200
72 50
3.3
29
25
22
18
15
-
-
45
3.7
27
23
20
16
13
-
-
67 45
3.4
37
33
30
27
23
20
16
39
3.7
34
31
27
24
21
17
14
62 41
3.3
41
41
37
34
31
27
24
36
3.6
36
36
33
29
26
22
19
57 40
3.3
40
40
37
33
30
26
23
35
3.6
35
35
32
29
25
22
19
1400
72 52
3.4
32
28
24
20
16
-
-
47
3.7
30
26
22
18
14
-
-
67 47
3.4
41
37
33
29
25
20
16
41
3.7
38
34
30
26
22
18
14
62 42
3.3
42
42
41
37
33
29
24
37
3.6
37
37
36
32
28
24
20
57 42
3.3
42
42
40
36
32
28
24
37
3.6
37
37
35
31
27
23
19
1600
72 54
3.4
35
30
26
21
16
-
-
49
3.7
33
28
24
19
14
-
-
67 49
3.4
45
40
35
31
26
21
17
43
3.7
41
37
33
28
24
19
14
62 44
3.3
44
44
44
39
35
30
25
39
3.6
39
39
39
34
30
25
20
57 43
3.3
43
43
43
39
34
29
25
39
3.6
39
39
39
34
29
25
20
1800
72 53
3.4
38
33
27
22
17
-
-
49
3.7
36
31
25
20
15
-
-
67 48
3.4
46
43
38
32
27
22
16
43
3.7
42
39
35
30
24
19
14
62 44
3.3
44
44
44
38
33
28
22
39
3.6
39
39
39
33
28
23
17
57 43
3.3
43
43
43
38
32
27
22
38
3.7
38
38
38
33
27
22
17
2000
72 53
3.4
41
35
29
23
17
-
-
48
3.7
39
33
27
21
15
-
-
67 48
3.4
48
46
40
34
28
22
16
42
3.7
42
41
37
31
25
19
14
62 43
3.3
43
43
43
37
31
25
19
38
3.7
38
38
38
32
26
20
14
57 42
3.3
42
42
42
37
31
25
19
38
3.7
38
38
38
32
26
20
14
115°F
125°F
1200
72 40
4.0
25
21
18
14
11
-
-
35
4.3
23
19
16
13
9
-
-
67 34
3.9
32
28
25
21
18
15
11
28
4.2
28
26
22
19
15
12
9
62 31
3.9
31
31
28
25
21
18
14
26
4.2
26
26
23
20
16
13
10
57 30
3.9
30
30
28
24
21
17
14
25
4.2
25
25
23
20
16
13
9
1400
72 42
4.0
28
24
20
16
12
-
-
38
4.3
26
22
18
14
10
-
-
67 36
4.0
35
32
28
24
20
16
11
30
4.3
30
29
25
21
17
13
9
62 32
3.9
32
32
31
27
23
19
15
28
4.2
28
28
26
22
18
14
10
57 32
3.9
32
32
31
27
23
19
15
27
4.3
27
27
26
22
18
14
10
1600
72 45
4.0
31
27
22
17
13
-
-
40
4.3
29
25
20
15
11
-
-
67 38
4.0
38
35
30
26
21
16
12
32
4.3
32
32
28
23
19
14
9
62 34
3.9
34
34
34
30
25
20
16
29
4.2
29
29
29
25
20
15
11
57 34
4.0
34
34
34
29
25
20
15
29
4.3
29
29
29
24
20
15
10
1800
72 44
4.0
34
29
24
18
13
-
-
39
4.4
32
27
22
16
11
-
-
67 37
4.0
37
36
33
27
22
17
11
31
4.3
31
31
30
25
20
14
9
62 34
4.0
34
34
34
28
23
18
12
29
4.3
29
29
29
23
18
13
8
57 33
4.0
33
33
33
28
23
17
12
29
4.3
29
29
29
23
18
13
7
2000
72 43
4.1
37
31
25
19
13
-
-
39
4.4
35
29
23
17
11
-
-
67 36
4.0
36
36
35
29
23
17
11
31
4.3
31
31
31
27
21
15
9
62
33
4.0
33
33
33
27
21
15
9
28
4.3
28
28
28
22
16
10
4
57
33
4.0
33
33
33
27
21
15
9
28
4.3
28
28
28
22
16
10
4
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.