beautypg.com

York DY 036 User Manual

Page 22

background image

343615-YTG-A-0807

22

Unitary Products Group

MODEL

TONNAGE

VOLTAGE

COMPRESSORS

OD FAN
MOTOR

FLA

ID

BLOWER

MOTOR

FLA

CONV

OUTLET

FLA

ELECTRIC HEATER

MODEL NO.

HEATER

KW

HEATER

AMPS

MIN.

CIRCUIT

AMPACITY

(AMPS)

MAX. FUSE/

BRKR

1

SIZE

(AMPS)

RLA

EACH

LRA

EACH

DY060

208-1-60

28.8

145.0

2.3

10.6

10.0

None

-

-

58.9

60

2CE04510506

4.0

19.2

58.9

60

2CE04510706

5.6

26.9

59.4

60

2CE04511006

8.0

38.5

73.8

80

2CE04511506

11.9

57.2

97.3

100

2CE04512006

15.9

76.4

121.3

125

2CE04513006

22.2

106.7

159.2

175

230-1-60

28.8

145.0

2.3

10.6

10.0

None

-

-

58.9

60

2CE04510506

5.3

22.1

58.9

60

2CE04510706

7.5

31.3

64.8

70

2CE04511006

10.6

44.2

81.0

90

2CE04511506

15.9

66.3

108.6

110

2CE04512006

21.2

88.3

136.2

150

2CE04513006

29.6

123.3

179.9

200

208-3-60

17.3

123.0

2.3

10.6

10.0

None

-

-

44.5

45

2CE04510525

2

4.0

11.1

44.5

45

2CE04510725

2

5.6

15.5

45.2

50

2CE04511025

8.0

22.2

53.5

60

2CE04511525

11.9

33.0

67.0

70

2CE04512025

15.9

44.1

80.9

90

2CE04513025

22.2

61.6

102.8

110

230-3-60

17.3

123.0

2.3

10.6

10.0

None

-

-

44.5

45

2CE04510525

2

5.3

12.7

44.5

45

2CE04510725

2

7.5

18.0

48.3

50

2CE04511025

10.6

25.5

57.6

60

2CE04511525

15.9

38.2

73.6

80

2CE04512025

21.2

51.0

89.5

90

2CE04513025

29.6

71.2

114.8

125

460-3-60

9.6

70.0

1.3

10.6

5.0

None

-

-

23.6

25

2CE04510746

2

6.8

8.2

23.6

25

2CE04511046

2

10.1

12.1

28.1

30

2CE04511546

2

13.6

16.4

33.3

35

2CE04512046

2

19.5

23.5

42.2

40

2CE04513046

2

28.8

34.6

56.2

60

575-3-60

7.4

53.0

1.3

10.6

4.0

None

-

-

18.5

20

2CE04511058

10.6

10.2

23.0

25

2CE04511558

15.9

15.3

29.4

30

2CE04512058

21.2

20.4

35.8

35

2CE04513058

30.4

29.3

46.9

45

1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block

accessories 2FB04700825 and 2FB04700846 are available for field installation.

TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET (CONT)