Unit dimensions, Unit clearances, Figure 8 - unit dimensions – York PREDATOR 150 User Manual

Page 13: Table 6: unit clearances, Detail a, Detail b, Detail c

background image

035-17311-002-A-0803

Unitary Products Group

13

NOTE:

A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.

Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion
air inlet or vent outlets.

FIGURE 8 - UNIT DIMENSIONS

F o r B a s e r a i l

D i m e n s i o n s

S e e D e t a i l A

8 9

2 7

5 9

5 0 - 3 / 4

4 - 1 / 4

6 - 3 / 1 6

1 7 - 3 / 1 6

2 4 - 3 / 1 6

3 0 - 3 / 1 6

C o n v e n i e n c e

P o w e r

O u t l e t

E n t r y

Ø 7 / 8

P o w e r

E n t r y

Ø 2 - 1 / 2

3 0 - 1 1 / 3 2

C o n t r o l

E n t r y

Ø 7 / 8

P o w e r

E n t r y

Ø 2 - 1 / 2

L E F T

F R O N T

F o r D r a i n

D i m e n s i o n s

S e e D e t a i l B

TABLE 6:

UNIT CLEARANCES

Top

*

*.

Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.

72”

Right

12”

Front

36”

Left

36”

Rear

†.

To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.

36”

Bottom

‡.

Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.

0”

5 - 1 / 4

B a s e

P a n

1 7 - 1 3 / 1 6

V i e w o f W a l l A c r o s s f r o m C o i l

G a s P i p e I n l e t

DETAIL A

3 - 3 / 4

3 - 9 / 1 6

2 - 3 / 8

DETAIL B

5 - 3 / 8

DETAIL C