beautypg.com

Clearances, Unit 4 point load, Unit 6 point load – York PREDATOR 150 User Manual

Page 12: Unit center of gravity, Unit weights, 6 point load weight, 4 point load weight, Figure 5 - unit 4 point load table 3: unit weights, Table 4: 6 point load weight, Table 5: 4 point load weight

background image

035-17311-002-A-0803

12

Unitary Products Group

Units may be moved or lifted with a forklift. Slotted openings
in the base rails are provided for this purpose.

LENGTH OF FORKS MUST BE A MINIMUM OF 60
INCHES.

CLEARANCES

All units require particular clearances for proper operation
and service. Installer must make provisions for adequate
ventilation air in accordance with applicable provisions of the
local building codes. Refer to Table 6 for clearances required
for combustible construction, servicing, and proper unit oper-
ation

.

Before lifting, make sure the unit weight is distrib-
uted equally on the rigging cables so it will lift evenly.

All panels must be secured in place when the unit is
lifted.

The condenser coils should be protected from rig-
ging cable damage with plywood or other suitable
material.

FIGURE 5 - UNIT 4 POINT LOAD

TABLE 3:

UNIT WEIGHTS

Model

Shipping Weight

*

(lb.)

*.

Weights include largest gas heat option.

Operating Weight

(lb.)

†.

54kW heater.

DM090

1056

1051

DM120

1121

1116

DM150

1200

1195

Econ.

85

84

w/ PE

150

148

Elec. Heat

2

49

49

D

A

C

B

L E F T

F R O N T

TABLE 4:

6 POINT LOAD WEIGHT

Model

Location (lbs.)

*

*.

Weights include largest gas heat option.

A

B

C

D

E

F

DM090

158

142

128

187

207

230

DM120

168

151

136

198

219

244

DM150

180

161

145

212

235

262

TABLE 5:

4 POINT LOAD WEIGHT

Model

Location (lbs.)

*

*.

Weights include largest gas heat option.

A

B

C

D

DM090

230

197

287

336

DM120

245

209

305

357

DM150

262

224

327

382

FIGURE 6 - UNIT 6 POINT LOAD

FIGURE 7 - UNIT CENTER OF GRAVITY

D

A

C

B

E

F

L E F T

F R O N T

FRONT

LEFT

47 1/2"

25 1/2"