beautypg.com

York SINGLE PACKAGE AIR CONDITIONING CH060 User Manual

Page 7

background image

036-21217-001-B-1203

Unitary Products Group

7

TABL

E

4: S

U

P

P

L

Y

AI

R

BL

OW

E

R

P

E

R

F

O

R

M

ANCE

CH060-12

0,

5 T

O

10 T

O

N

HO

RI

Z

O

NT

AL

M

O

DE

L

S

EXTERNAL STATIC PRESSURE - Inches W.C.

MODEL

SUPPLY

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

#

C

F

M

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1800

846

0.41

936

0.48

1024

0.56

1107

0.64

1195

0.74

1259

0.82

1325

0.90

1400

0.99

-

-

CH060

2000

917

0.54

999

0.62

1079

0.71

1157

0.79

1233

0.89

1305

0.98

-

-----

2200

994

0.70

1069

0.79

1142

0.88

1214

0.98

-

-

-

-

-

-----

3000

810

0.65

900

0.78

986

0.91

1066

1.04

1143

1.17

1221

1.32

1294

1.48

1363

1.63

1433

1.79

CH096

3200

851

0.78

938

0.91

1018

1.04

1095

1.18

1170

1.32

1236

1.42

1305

1.56

1380

1.74

1447

1.90

3400

892

0.91

974

1.05

1051

1.19

1125

1.33

1196

1.48

1266

1.64

1320

1.81

1390

1.90

-

-

3600

927

1.05

1006

1.20

1081

1.34

1152

1.50

1220

1.65

1287

1.81

1353

1.98

1405

2.07

1472

2.17

CH120

4000

1012

1.40

1085

1.56

1153

1.73

1220

1.89

1283

2.06

1345

2.23

1405

2.41

1464

2.59

1522

2.78

4400

1100

1.83

1166

2.00

1230

2.18

1292

2.37

1351

2.55

1410

2.74

1466

2.92

----

NOTE:

1. At higher evaporator airflows, and wet bulb conditions condensate carry-over may occur. Adjust airflow downward as necessary

.

2. Values include pressure drop from wet coil and clean filters.

3. Shaded areas indicate oversize motors

This manual is related to the following products: