Page 10: Front view, Utilities entry data

background image

036-21359-001-B-0302

10

Unitary Products Group

RETURN

AIR

SUPPLY

AIR

BOTTOM SUPPLY

AND RETURN

AIR OPENINGS

(See Note)

(B)
POWER WIRING
ENTRY

(A)
CONTROL WIRING
ENTRY

NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.

UNIT BASE WITH RAILS
Shown separately to illustrate
Bottom Duct openings and Power
Connection locations

12-1/2"

9-1/4"

8-1/8"

9-3/4"

3-3/4"

(B)
POWER WIRING
ENTRY

(A)
CONTROL WIRING
ENTRY

92"

CONDENSER
COILS

OPTIONAL COIL
GUARD KIT

COMPRESSOR
ACCESS
(See detail "X")

ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

BLOWER
ACCESS

BLOWER MOTOR
ACCESS

BLOWER
COMPARTMENT
ACCESS
(Auxiliary)

DOT PLUG
(For pressure
Drop Reading)

FRONT
VIEW

ELECTRIC HEAT
ACCESS

CONTROL BOX
ACCESS

21"

5"

9-3/4"

11-1/2"

2-3/4"

21-1/2"

33"

35"

5-7/8"

RETURN AIR

SUPPLY AIR

OUTDOOR AIR

OUTDOOR AIR
(Economizer)

24-1/4" (15 TON)
36-1/4" (20 TON)

48-5/8" (15TON)
52-5/8" (20TON)

125-1/4" (15 TON)
136-1/4" (20 TON)

HOLE

OPEN ING

SIZE

(DIA.)

USED FOR

A

1-1/8" KO

Con trol
Wir ing

Front

3/4" NPS (Fem.)

Bot tom

B

3-5/8" KO

Power
Wir ing

Front

3" NPS (Fem.)

Bot tom

C2-3/8" KO

Gas Pip ing (Front)

1

D

1-11/16" Hole

Gas Pip ing (Bot -
tom)

1,2

1

1" pip ing MPT re quired

2 Open ing in the bot tom of the unit can be lo cated by the slice
in the in su la tion.

UTILITIES ENTRY DATA

All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.

RETURN

AIR

SUPPLY

AIR

BOTTOM SUPPLY

AND RETURN

AIR OPENINGS

(See Note)

(B)
POWER WIRING
ENTRY

(A)
CONTROL WIRING
ENTRY

NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.

UNIT BASE WITH RAILS
Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations

12-1/2"

9-1/4"

8-1/8"

9-3/4"

3-3/4"

(B)
POWER WIRING
ENTRY

(A)
CONTROL WIRING
ENTRY

92"

CONDENSER
COILS

OPTIONAL
COIL GUARD
KIT

COMPRESSOR
ACCESS
(See detail "X")

ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

BLOWER
ACCESS

BLOWER MOTOR
ACCESS

BLOWER
COMPARTMENT
ACCESS
(Auxiliary)

DOT PLUG
(For pressure
Drop Reading)

FRONT
VIEW

CONTROL BOX
ACCESS

21"

5"

9-3/4"

11-1/2"

2-3/4"

21-1/2"

33"

35"

5-7/8"

46-5/8"

7-1/8"

6-3/8"

VENT AIR
OUTLET
HOODS

COMBUSTION
AIR INLET
HOOD

GAS HEAT
ACCESS

(C)
GAS SUPPLY
ENTRY

46-5/8"

11-1/8"

(D)
GAS SUPPLY
ENTRY

35-1/4

136-1/4

52-5/8

RETURN AIR

SUPPLY AIR

OUTDOOR AIR

OUTDOOR AIR
(Economizer)

Front

36"

Back

24" (Less Econo mizer)
49" (With Econo mizer)

Left Side (Fil ter Ac cess)

24" (Less Econo mizer)
36" (With Econo mizer)

Right Side (Cond. Coil)

36"

Be low Unit

1

2

0"

Above Unit

2

72" With 36" Maxi mum
Hori zon tal Over hang
(For Con denser Air
Dis charge)

1U nits (ap pli ca ble in U.S.A. only) may be in stalled on com bus ti ble floors
made from wood or class A, B or C roof cov er ing ma te rial.

2

Units must be in stalled ou doors. Over hang ing struc tures or shrubs should

not ob struct con denser air dis charge out let.

NOTE:
ELEC/ELEC Mod els: Units and duct work are ap proved for zero clear ance to
com bus ti ble ma te ri als when equipped with elec tric heat ers.

GAS/ELEC Mod els: A 1" clear ance must be pro vided be tween any
com bus ti ble ma te rial and the sup ply air duct work for a dis tance of 3 feet
from the unit.

The prod ucts of com bus tion must not be al lowed to ac cu mu late within a
con fined space and re cir cu late.

Lo cate unit so that the vent air out let hood is at least:

?

Three (3) feet above any forced air in let lo cated within 10 hori zon tal feet (ex -
clud ing those in te gral to the unit).

?

Four (4) feet be low, 4 hori zon tal feet from, or 1 foot above any door or grav ity
air in let into the build ing.

CLEARANCES