Maximum remote sense line drop compensation, Isolation, Environmental specification – Xantrex Technology XPR 150-40 User Manual
Page 77: Thermal specification, Humidity specification, Approvals
Specifications and Characteristics
Environmental Specification
Release 1.1
75
Maximum Remote Sense Line Drop Compensation
Minimum 3.8 V for each line, 5 V typical
Isolation
Environmental Specification
Thermal
Specification
Humidity
Specification
Approvals CSA certified to UL 3111-1, and CSA C22.2 No. 1010.1
FCC Part 15B and Industry Canada Class A
CE Marked for Low Voltage Directive and EMC Directive (Class A emissions)
AC Input to Output
1350 V
ac
AC Input to Chassis
1350 V
ac
Output to Chassis
600 V
ac
Operating Temperature Range
0°C–50°C
1
1. Consult the factory for operation below 0°C and above
50°C.
Storage Temperature Range
– 40°C–+ 85°C
Operating Humidity Range < 95% RH, Non-condensing
Storage Humidity Range
< 95% RH, Non-condensing
This manual is related to the following products: