4

Unitary Products Group

NOTE:

Do not exceed minimum/maximum CFM limits shown
under Air Flow Data.

APPLICATION LIMITATIONS

These units must be installed in accordance with all national
and local safety codes.

Air flow must be within the minimum and maximum limits

approved for electric heat, evaporator coils and outdoor units.

COOLING CAPACITY - COIL ONLY

*

MODEL COIL

RATED CFM ENTERING AIR °F (WET BULB)

MBH@ EVAPORATOR TEMPERATURE AND CORRESPONDING PRESSURE °F / PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

UNCASED UPFLOW

G1NA024S17G

800

72

27.4

25.0

22.3

19.4

67

25.3

22.9

20.3

17.5

62

20.8

18.4

15.9

13.4

57

16.9

14.6

12.2

9.4

G1NA030S17H

1000

72

35.2

32.0

28.6

24.8

67

32.4

28.6

25.3

21.9

62

26.6

23.6

21.5

18.7

57

25.2

22.7

20.2

17.6

G1NA030S17K

1000

72

39.6

36.0

32.1

27.9

67

36.4

33.2

29.5

25.7

62

29.9

27.2

24.2

21.0

57

28.1

25.6

22.7

19.8

G1NA036S17J

1200

72

49.3

44.9

39.9

34.7

67

45.4

41.3

36.7

32.0

62

37.2

33.8

30.1

26.2

57

35.0

28.3

28.3

24.6

G1NA036S17L

1200

72

59.9

54.5

48.5

42.6

67

55.1

51.1

44.6

38.9

62

45.2

41.1

36.6

31.9

57

42.5

38.7

34.4

30.0

G1NA036S21C

1200

72

49.3

44.9

39.9

34.7

67

45.4

41.3

36.7

32.0

62

37.2

33.8

30.1

26.2

57

35.0

31.8

28.3

24.6

G1NA042S24W

1400

72

86.7

73.0

59.2

44.9

67

69.4

57.2

45.2

33.1

62

54.0

42.3

33.4

26.8

57

46.4

40.0

33.4

26.8

G1NA048S21D

1400

72

62.4

56.8

50.5

44.4

67

57.4

53.2

46.5

40.5

62

47.1

42.8

38.1

33.2

57

44.3

40.3

35.8

31.2

G1NA060S24T

1800

72

95.4

82.1

68.4

54.0

67

76.4

64.1

52.2

39.9

62

59.6

47.4

38.6

32.4

57

51.2

44.8

38.6

32.4

*

See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

APPLICATION FACTOR-RATED
CFM VS. ACTUAL CFM

% OF RATED AIR FLOW 80% 90% RATED CFM 110% 120%

CAPACITY FACTOR

0.96 0.98

1.00

1.02

1.03

ENTERING AIR TEMPERATURE LIMITS

WET BULB TEMP. ºF

DRY BULB TEMP. ºF

Min.

Max.

Min.

Max.

57

72

65

95