beautypg.com

York GHD User Manual

Page 2

background image

036-21145-003 Rev. A (0403)

2

Unitary Products Group

COOLING CAPACITY - Coil Only

*

MODEL

RATED

CFM

ENTERING

AIR

°

F

(WET BULB)

MBH @ EVAPORATOR TEMPERATURE AND CORRESPONDING

PRESSURE °F / PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

UPFLOW "A" TYPE

G1FA024S14(T)

G1UA024S14

675

72

35.6

32.5

29.0

25.2

67

32.9

29.7

26.3

22.7

62

27.0

23.9

20.7

17.4

57

21.9

19.0

15.9

12.4

G1FA024S17(T)

G1UA024S17

850

72

35.6

32.5

29.0

25.2

67

32.9

29.7

26.3

22.7

62

27.0

23.9

20.7

17.4

57

21.9

19.0

15.9

12.4

G1FA030S14(T)

G1UA030S14

1025

72

38.9

35.4

31.6

27.6

67

33.9

30.3

26.8

23.0

62

27.3

23.7

22.5

18.0

57

22.6

20.1

17.5

14.8

G1FA036S14(T)
G1FA036S17(T)

G1UA036S14
G1UA036S17

1250

72

51.1

46.5

41.5

36.6

67

40.9

36.1

31.7

26.9

62

32.0

26.8

29.3

21.8

57

27.4

25.4

23.4

21.8

G1FA036S21(T)

G1UA036S21

1250

72

51.1

46.5

41.5

36.6

67

40.9

36.1

31.7

26.9

62

32.0

26.8

29.3

21.8

57

27.4

25.4

23.4

21.8

G1FA048S17(T)
G1FA048S21(T)

G1UA048S17

G1FUA048S21

1620

72

99.4

85.5

71.2

56.2

67

79.6

66.8

54.4

41.6

62

62.1

49.4

40.2

33.7

57

53.3

46.7

40.2

33.7

G1FA060S21(T)
G1FA060S24(T)

G1UA060S21
G1UA060S24

1850

72

118.7

100.0

81.1

61.5

67

95.0

78.4

61.9

45.4

62

74.0

58.0

45.7

36.7

57

63.6

54.8

45.7

36.7

*

- See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

(T) indicates models with factory installed thermal expansion valve.

Coil Only

*

MODEL

RATED

CFM

ENTERING

AIR

°

F

(WET BULB)

MBH @ EVAPORATOR TEMPERATURE AND CORRESPONDING PRESSURE

°F/ PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

HORIZONTAL DUCT TYPE

G1HD024

815

72

35.3

32.4

28.7

24.9

67

32.6

29.4

26.0

22.5

62

26.7

23.7

20.5

17.2

57

21.7

18.8

15.7

12.3

G1HD036

1192

72

57.9

52.7

47.1

41.5

67

46.4

41.1

35.9

30.4

62

36.2

30.4

26.5

24.7

57

31.1

28.7

26.5

24.7

G1HD048

1610

72

83.4

71.7

59.7

47.1

67

66.8

56.1

45.6

34.9

62

52.1

41.5

33.7

28.3

57

44.7

39.2

33.7

28.3

G1HD060

2100

72

133.0

112.4

90.9

69.2

67

106.5

87.9

69.4

50.0

62

83.0

65.0

51.3

41.1

57

71.2

61.4

51.3

41.1

*

See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

This manual is related to the following products: