NOTE:

A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.

NOTE:

If the unit includes gas heating, locate the unit so
the flue exhaust is at least:

Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).

Four (4) feet below, four (4) horizontal feet from, or one
(1) foot above any door or gravity air inlet into the build-
ing.

Four (4) feet from electric meters, gas meters, regula-
tors, and relief equipment.

.

TABLE 6:

UNIT CLEARANCES

Top

*

*.

Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.

72”

Right

12”

Front

†.

The products of combustion must not be allowed to
accumulate within a confined space and re-circulate.

36”

Left

36”

Rear

‡.

To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.

36”

Bottom

**

**.

Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.

0”

5 - 1 / 4

B a s e

P a n

1 7 - 1 3 / 1 6

V i e w o f W a l l A c r o s s f r o m C o i l

G a s P i p e I n l e t

DETAIL A

3 - 3 / 4

3 - 9 / 1 6

2 - 3 / 8

DETAIL B

5 - 3 / 8

DETAIL C

FIGURE 14 - BOTTOM DUCT OPENINGS (FROM ABOVE)

Return

Air

Supply

Air

32-11/16

6-13/16

6-13/16

6-13/16

21-3/16

19-3/16

17-3/16

7-1/8

14-23/32

16-3/8

18-1/16

19-5/8

63-1/2

27-1/2

18

24

21

12-5/16

LEFT

FRONT

Bottom

Condensate

Drain

Bottom

Power, Control and

Convenience Outlet

Wiring Entries

Bottom

Gas Supply Entry