15

FIGURE 3 - TYPICAL FIELD CONTROL WIRING DIAGRAM

TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE 1-1/2 - 3-1/2 TON (DNA018 - 042)

1

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

WET EVAPORATOR COIL

.01

.01

.01

.02

.03

.04

.05

.06

.07

.08

.09

.09

-

-

-

-

ECONOMIZER

2

.00

.00

.00

.01

.01

.01

.01

.02

.03

.04

.05

.06

-

-

-

-

FILTER FRAME KIT

.01

.02

.04

.06

.08

.10

.13

.16

.17

.18

.19

.20

-

-

-

-

1. Deduct these resistance values from the available external static pressure shown in Tables 10 and 11.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air

duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE 4 - 5 TON (DNA048 - 060)

1

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

WET EVAPORATOR COIL

-

-

-

-

-

-

-

.03

.04

.05

.06

.07

.07

.08

.09

.09

ECONOMIZER

2

-

-

-

-

-

-

-

.02

.02

.03

.03

.04

.04

.04

.05

.05

FILTER FRAME KIT

-

-

-

-

-

-

-

.04

.05

.05

.06

.07

.08

.09

.10

.11

1. Deduct these resistance values from the available external static pressure shown in Table 10 and 11.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct

system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

R

G

W

R

G

C

Y

Y

W

C

PROGRAMMABLE

THERMOSTAT ONLY

**

** = Minimum wire size of 18 AWG

wire should be used for all
field installed 24 volt wire.

THERMOSTAT

UNIT TERMINAL STRIP

NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.

24 VOLT
TRANSFORMER