York 12 SEER H*RC018 THRU 060 User Manual
Page 4
036-21137-004 Rev. C (0505)
4
Unitary Products Group
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.
2. Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
5. If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.
G1NA036S17L
63
–
–
63 + 15
73 + 12
–
–
–
–
–
701 + 15
702 + 12
–
–
–
G1NA048S21D
78
–
–
–
73 + 12
78 + 0
87 + 0
–
–
–
–
702 + 12
702 + 0
703 + 0
–
G1NA048S24P
63
–
–
–
73 + 13
78 + 2
87 + 1
–
–
–
–
702 + 13
702 + 2
703 + 1
–
G1NA060S24T
78
–
–
–
–
–
–
–
–
–
–
–
–
–
703 + 0
G1NF024SOF
63
–
–
–
–
–
–
–
–
–
–
–
–
–
–
G1NF036SOF
67
–
59 + 12
63 + 0
73 + 7
–
–
–
–
701 + 12
701 + 0
702 + 7
–
–
–
G1NF048SOF
78
–
–
–
–
78 + 21
87 + 6
–
–
–
–
–
702 + 21
703 + 6
–
G1NF060SOF
87
–
–
–
–
–
87 + 18
–
–
–
–
–
–
703 + 18
–
F(2,3)RP024N,H06(T)
61
53 + 4
59 + 4
–
–
–
–
–
701 + 4
701 + 4
–
–
–
–
–
F(2,3)RP030N06(T)
65
–
59 + 6
63 + 4
–
–
–
–
–
701 + 6
701 + 4
–
–
–
–
F(2,3)RP036N06(T)
75
–
–
63 + 4
73 + 8
–
–
–
–
–
701 + 4
702 + 8
–
–
–
F(2,3)RP042N06(T)
78
–
–
–
73 + 13
78 + 0
–
–
–
–
–
702 + 13
702 + 0
–
–
F(2,3)FP048N06(T)
84
–
–
–
73 + 16
78 + 10
87 + 11
–
–
–
–
702 + 16
702 + 10
703 + 11
–
F(2,3)FP060N06(T)
90
–
–
–
–
–
87 + 15
–
–
–
–
–
–
703 + 15
703
5
+ 5
F(2,3)FV060N06(T)
90
–
–
–
–
–
87 + 15
–
–
–
–
–
–
703 + 15
703 + 5
FOOTNOTES:
1. These orifices are factory mounted in the flow control device of each indoor coil and must be removed for TXV installation.
2. A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).
3. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011.
4. These orifices are factory mounted in the flow control device of each indoor coil. A TXV is factory mounted if the model number has a (T) suffix.
5. This TXV is factory mounted in indoor coils, if the model number has a (T) suffix.
Additional R-22 Charge / Orifice Size for Various Matched Systems (Continued)- 1 Phase
Outdoor Unit
H2RC018S06 H2RC024S06 H2RC030S06 H2RC036S06 H2RC042S06 H2RC048S06 H4RC060S06
Unit Orifice (s)
1
53
59
63
73
78
87
–
Factory R-22 Charge, lbs-oz.
4 - 9
4 - 7
5 - 8
5 - 3
6 - 13
7 - 7
8 - 15
Indoor Coil
5
Coil Orifice
4
Orifice or TXV Kit
2
- Additional Charge, Oz.
3