York 13 SEER - R410A CZB018 THRU 060 User Manual

Page 12

background image

246723-YTG-J-1006

12

Unitary Products Group

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

CZB02411

INDOOR COIL MODEL NO.

G2FD030S17

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

600

800

1000

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

19.2

19.4

22.0

23.0

26.2

21.5

21.2

22.1

23.8

26.5

23.8

25.7

22.3

24.6

26.8

S.C.

18.9

16.4

15.9

15.7

11.9

21.2

20.9

18.1

18.3

13.4

23.5

25.4

20.3

21.0

14.8

K.W.

1.8

1.9

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.9

1.8

1.8

75

T.C.

21.5

22.3

20.7

24.9

27.5

23.1

23.5

22.5

25.8

28.5

24.7

24.7

24.3

26.7

29.5

S.C.

21.2

18.3

14.9

15.5

12.4

22.8

21.3

17.3

17.7

13.8

24.4

24.4

19.8

19.9

15.2

K.W.

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

85

T.C.

20.3

20.8

21.4

23.9

26.8

22.3

23.0

22.3

24.8

27.5

24.3

25.2

23.3

25.7

28.2

S.C.

20.0

17.3

15.4

15.6

12.1

22.0

21.1

17.7

18.0

13.6

23.9

24.9

20.0

20.4

15.0

K.W.

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

95

T.C.

18.9

19.6

19.7

22.2

25.0

20.8

21.4

20.6

23.0

25.7

22.6

23.3

21.5

23.8

26.3

S.C.

18.6

16.5

14.3

14.5

11.5

20.5

19.8

16.5

16.8

12.9

22.3

23.0

18.7

19.1

14.3

K.W.

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.0

2.1

2.0

2.0

105

T.C.

17.4

18.3

18.0

20.4

23.2

19.2

19.8

18.9

21.2

23.8

21.0

21.4

19.7

22.0

24.5

S.C.

17.2

15.7

13.2

13.4

10.9

18.9

18.4

15.2

15.6

12.2

20.7

21.1

17.3

17.8

13.6

K.W.

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

115

T.C.

16.0

17.2

16.4

18.7

21.4

17.7

18.3

17.2

19.4

22.0

19.3

19.5

17.9

20.2

22.7

S.C.

15.8

15.0

12.1

12.4

10.3

17.4

17.1

14.0

14.4

11.6

19.1

19.2

15.9

16.5

12.8

K.W.

2.8

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

125

T.C.

14.6

15.9

14.8

17.0

19.6

16.2

16.7

15.5

17.7

20.3

17.7

17.6

16.2

18.4

21.0

S.C.

14.4

14.2

11.0

11.4

9.7

16.0

15.8

12.8

13.3

10.9

17.5

17.3

14.6

15.2

12.1

K.W.

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

MA08B

FC/MC24B

1.00

1.01

1.00

MA08B

FC/MC30B

1.00

1.01

1.00

MA08B

G*FD036H17

1.01

1.01

1.00

MV12B

MC24B

1.00

1.01

0.95

AHP24

1.00

1.01

1.00

AV24

1.00

1.00

0.95

F*FP030

1.00

1.00

1.00

FC/MC/PC/UC24

1.00

1.01

1.00

FC/MC/PC/UC30

1.00

1.01

1.00

G*FA036S14

1.00

1.01

1.00

G*FA036S17,21

1.00

1.00

1.00

G*FD035H14

1.00

1.00

1.00

G*FD036H17

1.01

1.01

1.00

HC30

0.98

0.98

1.00

HD24

0.98

0.98

1.00

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

PV8*A12

FC/MC/PC24A

1.02

1.02

0.95

PV9*A12

FC/MC/PC24A

1.02

1.02

0.95

PV9*B12

FC/MC/PC24B

1.02

1.02

0.95

PV8*A12

FC/MC/PC30A

1.02

1.02

0.95

PV9*A12

FC/MC/PC30A

1.02

1.02

0.95

PV9*B12

FC/MC/PC30B

1.02

1.02

0.95

PV8*A12

HC30

0.99

0.99

0.95

PV9*A12

HC30

0.99

0.99

0.95

PV8*A12

HD24

0.99

0.99

0.95

PV9*A12

HD24

0.99

0.99

0.95