York PREDATOR 90 User Manual
Page 15

246646-YTG-C-0606
Unitary Products Group
15
TABLE 7: COOLING CAPACITY DH102 (8-1/2 TON) UNIT
Air On
Evap. Coil
Temperature of Air on Condenser Coil 75°F
Temperature of Air on Condenser Coil 85°F
CFM
WB
(°F)
Tot.
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Tot.
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
2550
72 117.0
1.8
66.8
59.5
52.2
44.9
37.7
-
-
112.5
7.6
64.3
57.0
49.8
42.5
35.2
-
-
67 112.1
1.9
85.1
77.8
70.5
63.2
56.0
48.7
41.4
106.1
7.5
82.2
74.9
67.7
60.4
53.1
45.8
38.6
62 104.1
2.0
104.
99.2
92.0
84.7
77.4
70.2
62.9
98.1
7.4
98.1
93.4
86.1
78.8
71.6
64.3
57.0
57 104.5
1.9
104.
103.
96.0
88.7
81.5
74.2
66.9
97.5
7.4
97.5
96.7
89.4
82.2
74.9
67.6
60.4
2975
72 120.7
4.3
72.7
64.1
55.5
46.9
38.3
-
-
116.0
7.6
70.5
61.9
53.3
44.7
36.1
-
-
67 115.7
4.3
92.1
83.5
75.0
66.4
57.8
49.2
40.6
109.4
7.5
89.6
81.0
72.4
63.9
55.3
46.7
38.1
62 107.5
4.4
107.
105.
97.8
89.2
80.6
72.0
63.4
101.1
7.4
101.
98.8
92.2
83.6
75.0
66.4
57.8
57 107.8
4.4
107.
107.
102.
93.5
84.9
76.3
67.7
100.6
7.4
100.
100.
95.8
87.2
78.6
70.0
61.4
3400
72 124.5
6.8
78.6
68.7
58.8
48.9
39.0
-
-
119.6
7.6
76.6
66.7
56.8
46.9
37.0
-
-
67 119.3
6.8
99.2
89.3
79.4
69.5
59.6
49.6
39.7
112.7
7.5
97.1
87.1
77.2
67.3
57.4
47.5
37.6
62 110.8
6.9
110.
110.
103.
93.7
83.8
73.9
63.9
104.2
7.4
104.
104.
98.3
88.4
78.5
68.6
58.6
57 111.2
6.8
111.
111.
108.
98.3
88.3
78.4
68.5
103.7
7.4
103.
103.
102.
92.2
82.3
72.4
62.4
3825
72 125.4
6.9
83.4
72.2
60.9
49.6
38.3
-
-
120.8
7.7
81.8
70.5
59.2
47.9
36.6
-
-
67 120.2
6.9
104.
93.5
82.2
70.9
59.6
48.3
37.0
113.9
7.6
103.
91.8
80.5
69.2
57.9
46.6
35.4
62 111.6
6.9
111.
111.
108.
96.7
85.4
74.1
62.8
105.3
7.5
105.
105.
102.
91.1
79.8
68.5
57.2
57 112.0
6.9
112.
112.
110.
99.2
87.9
76.6
65.3
104.7
7.5
104.
104.
104.
92.7
81.4
70.1
58.8
4250
72 126.3
6.9
88.3
75.6
62.9
50.3
37.6
-
-
122.1
7.7
87.0
74.3
61.6
49.0
36.3
-
-
67 121.0
6.9
110.
97.6
85.0
72.3
59.6
46.9
34.3
115.1
7.6
109.
96.5
83.8
71.1
58.5
45.8
33.1
62 112.4
7.0
112.
112.
112.
99.8
87.1
74.4
61.8
106.4
7.5
106.
106.
106.
93.8
81.1
68.4
55.8
57 112.8
6.9
112.
112.
112.
100.
87.5
74.8
62.2
105.8
7.5
105.
105.
105.
93.2
80.5
67.8
55.2
Temperature of Air on Condenser Coil 95°F
Temperature of Air on Condenser Coil 105°F
2550
72 108.0
13.4
61.8
54.6
47.3
40.0
32.8
-
-
99.4
11.5
59.2
52.0
44.7
37.4
30.2
-
-
67 100.0
13.1
79.3
72.1
64.8
57.5
50.3
43.0
35.7
90.8
11.2
75.4
68.1
60.8
53.6
46.3
39.0
31.7
62 92.0
12.8
92.0
87.5
80.3
73.0
65.7
58.5
51.2
82.0
11.0
82.0
79.8
72.7
65.4
58.2
50.9
43.6
57 90.5
12.9
90.5
90.2
82.9
75.6
68.3
61.1
53.8
83.3
11.1
83.3
82.3
75.1
67.8
60.5
53.2
46.0
2975
72 111.3
10.9
68.2
59.7
51.1
42.5
33.9
-
-
102.8
10.3
65.7
57.2
48.6
40.0
31.4
-
-
67 103.1
10.7
87.1
78.5
69.9
61.4
52.8
44.2
35.6
93.9
10.0
83.3
74.7
66.1
57.5
48.9
40.3
31.7
62 94.8
10.4
94.8
92.6
86.6
78.0
69.4
60.9
52.3
84.8
9.8
84.8
83.7
79.0
70.4
61.8
53.2
44.6
57 93.3
10.5
93.3
93.1
89.5
80.9
72.3
63.7
55.1
86.2
9.9
86.2
85.7
81.5
72.9
64.3
55.7
47.1
3400
72 114.7
8.4
74.6
64.7
54.8
44.9
35.0
-
-
106.2
9.1
72.3
62.3
52.4
42.5
32.6
-
-
67 106.2
8.2
94.9
85.0
75.1
65.2
55.3
45.3
35.4
97.0
8.9
91.2
81.2
71.3
61.4
51.5
41.6
31.7
62 97.7
8.0
97.7
97.7
93.0
83.1
73.2
63.3
53.3
87.6
8.7
87.6
87.6
85.2
75.3
65.4
55.5
45.6
57 96.1
8.1
96.1
96.1
96.0
86.1
76.2
66.3
56.4
89.1
8.7
89.1
89.1
88.0
78.1
68.1
58.2
48.3
3825
72 116.3
8.4
80.2
68.9
57.6
46.3
35.0
-
-
107.6
9.1
78.0
66.7
55.4
44.1
32.9
-
-
67 107.7
8.3
101.
90.2
78.9
67.6
56.3
45.0
33.7
98.2
8.9
95.0
86.7
75.4
64.1
52.8
41.6
30.3
62 99.1
8.1
99.1
99.1
96.7
85.4
74.1
62.8
51.6
88.8
8.7
88.8
88.8
87.6
76.3
65.0
53.7
42.4
57 97.5
8.1
97.5
97.5
97.4
86.2
74.9
63.6
52.3
90.2
8.8
90.2
90.2
89.7
78.4
67.1
55.8
44.5
4250
72 117.9
8.4
85.7
73.0
60.3
47.7
35.0
-
-
108.9
9.2
83.8
71.1
58.5
45.8
33.1
-
-
67 109.2
8.3
108.
95.3
82.7
70.0
57.3
44.7
32.0
99.5
8.9
98.9
92.2
79.5
66.9
54.2
41.5
28.9
62 100.5
8.1
100.
100.
100.
87.8
75.1
62.4
49.8
89.9
8.8
89.9
89.9
89.9
77.2
64.6
51.9
39.2
57 98.9
8.1
98.9
98.9
98.9
86.2
73.5
60.8
48.2
91.3
8.8
91.3
91.3
91.3
78.7
66.0
53.3
40.7
Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
2550
72 90.8
9.6
56.6
49.4
42.1
34.8
27.5
-
-
82.2
7.8
54.0
46.8
39.5
32.2
24.9
-
-
67 81.6
9.4
71.4
64.1
56.8
49.6
42.3
35.0
27.8
72.3
7.5
67.4
60.1
52.9
45.6
38.3
31.0
23.8
62 72.1
9.2
72.1
72.1
65.1
57.9
50.6
43.3
36.0
62.1
7.3
62.1
62.1
57.6
50.3
43.0
35.7
28.5
57 76.2
9.3
76.2
74.5
67.2
59.9
52.7
45.4
38.1
69.0
7.5
69.0
66.7
59.4
52.1
44.8
37.6
30.3
2975
72 94.3
9.7
63.3
54.7
46.1
37.5
28.9
-
-
85.8
9.1
60.8
52.2
43.6
35.0
26.4
-
-
67 84.7
9.4
79.4
70.8
62.2
53.6
45.0
36.4
27.8
75.4
8.8
75.4
66.9
58.3
49.8
41.2
32.6
24.0
62 74.8
9.2
74.8
74.8
71.3
62.7
54.1
45.5
36.9
64.8
8.6
64.8
64.8
63.6
55.0
46.4
37.8
29.2
57 79.1
9.3
79.1
78.2
73.6
65.0
56.4
47.8
39.2
71.9
8.8
71.9
70.8
65.6
57.0
48.4
39.8
31.3
3400
72 97.7
9.8
69.9
60.0
50.0
40.1
30.2
-
-
89.3
10.5
67.5
57.6
47.7
37.7
27.8
-
-
67 87.8
9.5
87.4
77.5
67.6
57.7
47.8
37.8
27.9
78.6
10.1
78.6
73.7
63.8
53.9
44.0
34.1
24.2
62 77.6
9.3
77.6
77.6
77.4
67.5
57.6
47.7
37.8
67.5
9.9
67.5
67.5
67.5
59.7
49.8
39.9
30.0
57 82.0
9.4
82.0
82.0
79.9
70.0
60.1
50.2
40.3
74.9
10.1
74.9
74.9
71.9
62.0
52.0
42.1
32.2
3825
72 98.8
9.8
75.9
64.6
53.3
42.0
30.7
-
-
90.1
10.6
73.7
62.5
51.2
39.9
28.6
-
-
67 88.8
9.5
88.6
83.3
72.0
60.7
49.4
38.1
26.8
79.3
10.2
79.3
79.3
68.5
57.2
46.0
34.7
23.4
62 78.5
9.4
78.5
78.5
78.4
67.1
55.8
44.5
33.2
68.2
10.0
68.2
68.2
68.2
57.9
46.6
35.3
24.1
57 82.9
9.5
82.9
82.9
81.9
70.6
59.3
48.0
36.7
75.6
10.1
75.6
75.6
74.1
62.8
51.5
40.2
28.9
4250
72 100.0
9.9
81.9
69.2
56.6
43.9
31.2
-
-
91.0
10.6
80.0
67.3
54.7
42.0
29.3
-
-
67 89.8
9.6
89.8
89.1
76.4
63.7
51.0
38.4
25.7
80.0
10.3
80.0
80.0
73.2
60.6
47.9
35.2
22.6
62 79.3
9.4
79.3
79.3
79.3
66.7
54.0
41.3
28.7
68.8
10.1
68.8
68.8
68.8
56.1
43.5
30.8
18.1
57 83.8
9.5
83.8
83.8
83.8
71.2
58.5
45.8
33.2
76.3
10.2
76.3
76.3
76.3
63.7
51.0
38.3
25.6
1
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.