APPLYING FILTER PRESSURE DROP TO

DETERMINE SYSTEM AIRFLOW

To determine the approximate airflow of the unit with a filter in place, fol-
low the steps below:

1.

Select the filter type.

2.

Determine the External System Static Pressure (ESP) without the
filter.

3.

Select a filter pressure drop from the table based upon the number
of return air openings or return air opening size and add to the
ESP from Step 2 to determine the total system static.

4.

If total system static matches a ESP value in the airflow table (i.e.
0.20, 0.60, etc,) the system airflow corresponds to the intersection
of the ESP column and Model/Blower Speed row.

5.

If the total system static falls between ESP values in the table (i.e.
0.58, 0.75, etc.), the static pressure may be rounded to the nearest
value in the table determining the airflow using Step 4 or calculate
the airflow by using the following example.

Example: For a 120,000 Btuh furnace operating on high speed blower,
it is found that total system static is 0.58" w.c. To determine the system
airflow, complete the following steps:

1.

Obtain the airflow values at 0.50" & 0.60" ESP.

Airflow @ 0.50": 2152 CFM
Airflow @ 0.60": 2042 CFM

2.

Subtract the airflow @ 0.50" from the airflow @ 0.60" to obtain air-
flow difference.

2042 - 2152 = -110 CFM

3.

Subtract the total system static from 0.50" and divide this differ-
ence by the difference in ESP values in the table, 0.60" - 0.50", to
obtain a percentage.

(0.58 - 0.50) / (0.60 - 0.50) = 0.8

4.

Multiply percentage by airflow difference to obtain airflow reduc-
tion.

(0.8) x (-110) = -88

5.

Subract airflow reduction value to airflow @ 0.50" to obtain actual
airflow @ 0.58" ESP.

2152 - 88 = 2064

FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL

MODEL NO.

DESCRIPTION

USED WITH

1NP0347

PROPANE (LP) CONVERSION KIT

ALL MODELS

1CT0302

CONCENTRIC INTAKE/VENT 2”

ALL MODELS EXCEPT 120 MBH

1CT0303

CONCENTRIC INTAKE/VENT 3”

ALL MODELS

1PS0904

HIGH ALTITUDE PRESSURE SWITCH KIT

(Does Not Include Orifices)

40

1PS0901

60/100/120

1PS0902

80/1200

1PS0903

80/1600

1NK0301

CONDENSATE NEUTRALIZER KIT

ALL MODELS

1HT0901

SIDEWALL VENT TERMINATION KIT 3”

ALL MODELS

1HT0902

SIDEWALL VENT TERMINATION KIT 2”

ALL MODELS

1CB0314

COMBUSTIBLE FLOOR BASE

These kits are required in downflow application when using G*F*

series coils. These kits are not required with MC/FC series coils,
but please ensure that the coil and furnace are secured and that

there are noair leaks.

14-1/2” CABINET

1CB0317

17-1/2” CABINET

1CB0321

21” CABINET

1CB0324

24 1/2” CABINET

1TK0914

COIL TRANSITION KIT

14-1/2” CABINET

1TK0917

17-1/2” CABINET

1TK0921

21” CABINET

1TK0924

24 1/2” CABINET

1VK0901

3-WAY TRANSITION KIT

All MODELS

This manual is related to the following products: