NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m
3
/min).
2. Motor voltage at 115 V.
3. NR = Operation at this static pressure is not recommended.
FILTER PERFORMANCE
The airflow capacity data published in Table 18 represents blower per-
formance WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the filter being
used or select an appropriate value from the Table 19.
NOTE: The filter pressure drop values in Table 19 are typical values for
the type of filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter manufactur-
ers.
TABLE 18: Blower Performance CFM
MODELS
Input/
Airflow/
Cabinet
Speed
Tap
Airflow with Top Return - without Filters (CFM)
Airflow with Top Return - without Filters (m
3
min)
External Static Pressure, Inches W.C.
External Static Pressure, Inches (kPa)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0.025 0.050 0.075 0.099 0.124 0.149 0.174 0.199 0.224 0.249
40/1200/A
High
1635
1590
1535
1480
1415
1340
1280
1185
NR
NR
46
45
43
42
40
38
36
34
NR
NR
Med-High 1179
1170
1160
1140
1135
1098
1048
1026
NR
NR
33
33
33
32
32
31
30
29
NR
NR
Med-Low
969
967
967
959
938
905
860
802
NR
NR
27
27
27
27
27
26
24
23
NR
NR
Low
774
753
745
726
698
674
652
612
NR
NR
22
21
21
21
20
19
18
17
NR
NR
60/1200/B
High
1687
1652
1631
1595
1557
1511
1456
1382
1313
1211
48
47
46
45
44
43
41
39
37
34
Med-High 1193
1183
1173
1162
1142
1115
1076
1036
982
950
34
33
33
33
32
32
30
29
28
27
Med-Low
933
933
921
911
902
872
825
793
771
712
26
26
26
26
26
25
23
22
22
20
Low
752
745
731
718
698
652
602
580
536
496
21
21
21
20
20
18
17
16
15
14
80/1200/B
High
1686
1658
1623
1572
1534
1465
1391
1305
1202
1091
48
47
46
44
43
41
39
37
34
31
Med-High 1257
1223
1218
1203
1177
1142
1094
1026
939
874
36
35
34
34
33
32
31
29
27
25
Med-Low
977
982
976
955
934
899
843
791
738
686
28
28
28
27
26
25
24
22
21
19
Low
775
777
757
733
698
663
627
584
549
490
22
22
21
21
20
19
18
17
16
14
80/1600/C
High
2071
2026
1981
1935
1864
1796
1713
1625
1532
1401
59
57
56
55
53
51
48
46
43
40
Med-High 1583
1590
1569
1554
1532
1502
1457
1409
1327
1221
45
45
44
44
43
43
41
40
38
35
Med-Low 1256
1275
1275
1288
1275
1265
1232
1187
1126
1023
36
36
36
36
36
36
35
34
32
29
Low
937
939
936
945
942
936
912
874
810
726
27
27
26
27
27
26
26
25
23
21
100/1600/C
High
1996
1961
1938
1896
1836
1779
1707
1625
1531
1399
56
56
55
54
52
50
48
46
43
40
Med-High 1449
1480
1495
1488
1488
1449
1417
1368
1299
1208
41
42
42
42
42
41
40
39
37
34
Med-Low 1167
1192
1192
1187
1202
1192
1182
1140
1097
1018
33
34
34
34
34
34
33
32
31
29
Low
932
900
871
840
805
761
710
663
641
623
26
25
25
24
23
22
20
19
18
18
100/2000/C
High
2404
2320
2225
2138
2034
1924
1816
1692
1559
1422
68
66
63
61
58
54
51
48
44
40
Med-High 2018
1955
1883
1815
1750
1670
1586
1497
1394
1246
57
55
53
51
50
47
45
42
39
35
Med-Low 1626
1581
1531
1488
1418
1363
1291
1225
1123
964
46
45
43
42
40
39
37
35
32
27
Low
1336
1291
1249
1205
1155
1091
1018
951
884
759
38
37
35
34
33
31
29
27
25
21
120/2000/D
High
2520
2432
2353
2251
2152
2042
1947
1815
1701
1525
71
69
67
64
61
58
55
51
48
43
Med-High 2018
1979
1945
1911
1863
1779
1705
1599
1493
1353
57
56
55
54
53
50
48
45
42
38
Med-Low 1586
1545
1501
1457
1407
1351
1287
1216
1081
926
45
44
42
41
40
38
36
34
31
26
Low
1321
1266
1213
1163
1111
1071
987
864
763
700
37
36
34
33
31
30
28
24
22
20
TABLE 19: Filter Performance - Pressure Drop Inches W.C. and (kPa)
Airflow Range
Minimum
Opening Size
Filter Type
Disposable
Washable Fiber
Pleated
CFM
m
3
/min
in
2
cm
2
In W.C.
kPA
In W.C.
kPA
In W.C.
kPA
0 - 750
0 - 21.4
230
1484
0.01
0.00249
0.01
0.00249
0.15
0.03736
751 - 1000
21.25 - 28.32
330
2129
0.05
0.01245
0.05
0.01245
0.20
0.04982
1001 - 1250
28.33 - 35.40
330
2129
0.10
0.02491
0.10
0.02491
0.20
0.04982
1251 - 1500
35.41 - 42.48
330
2129
0.10
0.02491
0.10
0.02491
0.25
0.06227
1501 - 1750
42.49 - 49.55
380
2452
0.15
0.03736
0.14
0.03487
0.30
0.07473
1751 - 2000
49.56 - 56.63
380
2542
0.19
0.04733
0.18
0.04484
0.30
0.07473
2001 & Above
56.64 - Above
463
2987
0.19
0.04733
0.18
0.04484
0.30
0.07473