beautypg.com

Table 1: sound power rating, Sound power rating, Capacity ratings - (ari 210/240) – York DF 072 User Manual

Page 8: Gas heat ratings, 2 stage gas heat ratings

background image

254599-YTG-C-0807

8

Unitary Products Group

TABLE 1: SOUND POWER RATING

1

UNIT

SIZE

CFM

ESP

BLOWER

SOUND POWER (db 10

-12

Watts)

Octave Band Centerline Frequency (Hz)

SWL

dB(A)

dB(A)

@

10Ft.

2

IWG

SPEED

KW

63

125

250

500

1,000

2,000

4,000

8,000

072

2,200

0.3

HIGH

1.35

87

87

77

70

72

65

60

55

77

44

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The

dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.

2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 210/240)

1

1. 80/67°F Indoor and 95°F outdoor.

MODEL

MBH

EER

2

2. EER = Energy Efficiency Ratio at full load - the cooling

capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).

DF072

70.5

10.4

TABLE 3: GAS HEAT RATINGS

1

1. All units are single-stage heating.

MODEL

MBH

INPUT

MBH

OUTPUT

AFUE

(%)

TEMP

RISE ºF

DF072N08
DF072N10

100
125

80

100

80.5
80.3

25 - 55
35 - 65

TABLE 4: 2 STAGE GAS HEAT RATINGS

MODEL

1

1. Models are 3Ø only.

MBH INPUT

MBH OUTPUT

STEADY STATE EFFICIENCY

RISE

MINIMUM HEATING

AIRFLOW (CFM)

1

ST

STAGE 2

ND

STAGE 1

ST

STAGE 2

ND

STAGE

1

ST

STAGE

2

ND

STAGE

MIN.

MAX.

DF072D06

45

75

35.8

60.8

79.4

81.1

35

70

1230

DF072D10

75

125

60.4

100.6

80.5

80.5

45

75

1230