beautypg.com

15 df physical data, 16 electric heat correction factors, 17 voltage limitations – York DF 072 User Manual

Page 14

background image

254599-YTG-C-0807

14

Unitary Products Group

TABLE 15: DF PHYSICAL DATA

MODELS

DF

072

EVAPORATOR

BLOWER

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

Fan Motor HP (Direct Drive)

1

Fan Motor HP (Belt Drive)

1 1/2

EVAPORATOR

COIL

Rows Deep

4

Fins Per Inch

13

Face Area (Sq. Ft.)

5.1

CONDENSER

FANS

Propeller Dia. (in.)

24

Fan Motor Hp

1/2

Nom. CFM

4200

CONDENSER

COILS

Rows Deep

2

Fins Per Inch

18

Face Area (Sq. Ft.)

17.1

COMPRESSOR

(Qty. Per Unit)

Recip Type

1

AIR

FILTERS

Quantity Per Unit (15” X 20” X 1” or 2“)

2

Quantity Per Unit (14” X 25” X 1” or 2“)

1

Total Face Area (sq. ft.)

6.3

CHARGE

Refrigerant 22

(lbs./oz.)

11/10

TABLE 16: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTIPLIER

208

208

0.75

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 17: VOLTAGE LIMITATIONS

1

1. Utilization Range “A” in accordance with ARI Standard

110.

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-3-60

187

252

460-3-60

432

504

575-3-60

540

630