11 electrical data - df072 belt drive, W/o powered conv. outlet, 12 electrical data - df072 direct drive – York DF 072 User Manual
Page 12

254599-YTG-C-0807
12
Unitary Products Group
TABLE 11: ELECTRICAL DATA - DF072 BELT DRIVE W/O POWERED CONV. OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
ELECTRIC HEATER
MODEL NO.
HEATER
KW
HEATER
AMPS
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
DF072
(6.0)
208-3-60
20.7
156.0
2.3
5.2
0.0
None
-
-
33.4
45
2CE04510525
2
4
11.1
33.4
45
2CE04510725
2
5.6
15.5
33.4
45
2CE04511025
8
22.2
34.3
45
2CE04511525
11.9
33.0
47.8
50
2CE04512025
15.9
44.1
61.7
70
2CE04513025
22.2
61.6
83.5
90
230-3-60
20.7
156.0
2.3
5.2
0.0
None
-
-
33.4
45
2CE04510525
2
5.3
12.7
33.4
45
2CE04510725
2
7.5
18.0
33.4
45
2CE04511025
10.6
25.5
38.4
50
2CE04511525
15.9
38.2
54.3
60
2CE04512025
21.2
51.0
70.2
80
2CE04513025
29.6
71.2
95.5
100
460-3-60
10.0
75.0
1.3
2.6
0.0
None
-
-
16.4
25
2CE04510746
2
6.8
8.2
16.4
25
2CE04511046
2
10.1
12.1
18.4
25
2CE04511546
2
13.6
16.4
23.7
25
2CE04512046
2
19.5
23.5
32.6
35
2CE04513046
2
28.8
34.6
46.6
50
575-3-60
8.2
54.0
1.3
2.0
0.0
None
-
-
13.3
20
2CE04511058
10.6
10.2
15.2
20
2CE04511558
15.9
15.3
21.6
25
2CE04512058
21.2
20.4
28
30
2CE04513058
30.4
29.3
39.1
40
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 12: ELECTRICAL DATA - DF072 DIRECT DRIVE W/O POWERED CONV. OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
ELECTRIC HEATER
MODEL NO.
HEATER
KW
HEATER
AMPS
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
DF072
(6.0)
208-3-60
20.7
156.0
2.3
10.6
0.0
None
-
-
38.8
50
2CE04510525
2
4.0
11.1
38.8
50
2CE04510725
2
5.6
15.5
38.8
50
2CE04511025
8.0
22.2
41.0
50
2CE04511525
11.9
33.0
54.5
60
2CE04512025
15.9
44.1
68.4
70
2CE04513025
22.2
61.6
90.3
100
230-3-60
20.7
156.0
2.3
10.6
0.0
None
-
-
38.8
50
2CE04510525
2
5.3
12.7
38.8
50
2CE04510725
2
7.5
18.0
38.8
50
2CE04511025
10.6
25.5
45.1
50
2CE04511525
15.9
38.2
61.1
70
2CE04512025
21.2
51.0
77.0
80
2CE04513025
29.6
71.2
102.3
110
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.