beautypg.com

Technical reference, Ungrounded. %rh ranges (on, Bulb – Watlow Electric Ramping and Profiling Microprocessor-Based Control SERIES 1500 User Manual

Page 81: Channel and are user selectable as, Solid state relay, 0.5a @ 24vac, Upon channel #1 rtd, 1 thru, Communlcatlons, 3 barrier, Power

background image

Technical Reference

Temperature ranges:

.. -100

1400°F

K t/c:

-100 to 2500°F

R t/c:

500 to 3200°F

RTD. -99.9 to 9999°F

_*

or

-73 to 760°C

o r

-73 to 1371 °C

or 260 to 1760°C

or _-99.9 to 537.7%

T/C inputs must be

ungrounded.

%RH ranges (on

channel #2 only) and user selectable. Range limits are 0.0 to

.

100.0% RH Input types:

RTD: % RH

IS

based

upon Channel #1

RTD

as

dry

bulb

and Channel #2 RTD as

l

0-5/DC:’ Direct % RH signal on Channel #2.

Dual RTD input includes analog retransmit of input signal levels: -0.5 to 5.0VDC

for Temp

Dual T/C

and 0 to 0.5VDC for %RH.

inp

LSD. 0° = 0

ut includes analog

retransmit of input signal levels: 1.5625mV

per

Volts.

Calibration offset of input signals.

l

RTD: ±10.0°F or °C.:

l

T/C: ±10° or °C.

Outputs

l

Control outputs are two per channel: heat & cool (humidify & de-humidify) action.

l

Solid state relay, 0.5A @ 24VAC

min,

253VAC max. opto-isolated, zero cross

switching or,

l

DC switched open collector solid state switches, 10VDC, 5mA.

l

Auxiliary discrete ouputs are displayed

as

Event

#1 thru

#4 for each

channel and

are user selectable as:

l

Solid state relay, 0.5A @ 24VAC

min, 253VAC max, opto-isolated, zero cross

switching or,

l

DC switched open collector solid state switches, 10VDC, 5mA.

.

Eight event outputs programmed per step,

or

l

Six event outputs programmed per step, an1 alarm output per channel.

Accuracy

l

Calibration Accuracy and Sensor Conformity: ± 0.25% of span, ± 1 digit (± 1% wet/

dry % RH) at 77°F ± 5°F ambient rated line voltage ± 1%.

l

Accuracy Span: 1000°F or 540°C minimum.

l

Temperature Stability:

l

Voltage Stability: ±

±2µV / ° F ambient.

0.01% of span / % of rated line voltage.

Communlcatlons

l

Serial data communications.

l

RS422A or RS-423A (RS232C Compatible) 1200 Baud.

l

Electrically isolated.

l

All o perator indications and controls.

l

RS-422 with ANSI X3.28 subparagraph 2.2-A.3 protocol, RS-423 with XON/XOFF

protocol.

Terminals

l

36 each #6 screws on

3 barrier

strips.

l

Communications: DB-15 female receptacle.

Power

.

115/230VAC ±1 O%, 50/60Hz.

l

Data retention upon power failure via Lithuim battery.

l

Optional battery backup real time clock.

Operating Environment

30 to 130°F/0-55°C.

l

O-9O% RH, non-condensing.

Dimensions

•Height: 6.0 in.

•Width: 6.0 in.

.

. Overall depth:

8.8 in:

l

Behind panel depth:

7.5 in.

l

Weight:

4.5 lb.

Specifications, Appendix

WATLOW Series 1500 User's Manual

81

-99 -99 3200 °F

999.9 -99.9 999.9 °F