Technical Reference
Temperature ranges:
.. -100
1400°F
K t/c:
-100 to 2500°F
R t/c:
500 to 3200°F
RTD. -99.9 to 9999°F
_*
or
-73 to 760°C
o r
-73 to 1371 °C
or 260 to 1760°C
or _-99.9 to 537.7%
T/C inputs must be
ungrounded.
%RH ranges (on
channel #2 only) and user selectable. Range limits are 0.0 to
.
100.0% RH Input types:
RTD: % RH
IS
based
upon Channel #1
RTD
as
dry
bulb
and Channel #2 RTD as
l
0-5/DC:’ Direct % RH signal on Channel #2.
Dual RTD input includes analog retransmit of input signal levels: -0.5 to 5.0VDC
for Temp
Dual T/C
and 0 to 0.5VDC for %RH.
inp
LSD. 0° = 0
ut includes analog
retransmit of input signal levels: 1.5625mV
per
Volts.
Calibration offset of input signals.
l
RTD: ±10.0°F or °C.:
l
T/C: ±10° or °C.
Outputs
l
Control outputs are two per channel: heat & cool (humidify & de-humidify) action.
l
Solid state relay, 0.5A @ 24VAC
min,
253VAC max. opto-isolated, zero cross
switching or,
l
DC switched open collector solid state switches, 10VDC, 5mA.
l
Auxiliary discrete ouputs are displayed
as
Event
#1 thru
#4 for each
channel and
are user selectable as:
l
Solid state relay, 0.5A @ 24VAC
min, 253VAC max, opto-isolated, zero cross
switching or,
l
DC switched open collector solid state switches, 10VDC, 5mA.
.
Eight event outputs programmed per step,
or
l
Six event outputs programmed per step, an1 alarm output per channel.
Accuracy
l
Calibration Accuracy and Sensor Conformity: ± 0.25% of span, ± 1 digit (± 1% wet/
dry % RH) at 77°F ± 5°F ambient rated line voltage ± 1%.
l
Accuracy Span: 1000°F or 540°C minimum.
l
Temperature Stability:
l
Voltage Stability: ±
±2µV / ° F ambient.
0.01% of span / % of rated line voltage.
Communlcatlons
l
Serial data communications.
l
RS422A or RS-423A (RS232C Compatible) 1200 Baud.
l
Electrically isolated.
l
All o perator indications and controls.
l
RS-422 with ANSI X3.28 subparagraph 2.2-A.3 protocol, RS-423 with XON/XOFF
protocol.
Terminals
l
36 each #6 screws on
3 barrier
strips.
l
Communications: DB-15 female receptacle.
Power
.
115/230VAC ±1 O%, 50/60Hz.
l
Data retention upon power failure via Lithuim battery.
l
Optional battery backup real time clock.
Operating Environment
30 to 130°F/0-55°C.
l
O-9O% RH, non-condensing.
Dimensions
•Height: 6.0 in.
•Width: 6.0 in.
.
. Overall depth:
8.8 in:
l
Behind panel depth:
7.5 in.
l
Weight:
4.5 lb.
Specifications, Appendix
WATLOW Series 1500 User's Manual
81
-99 -99 3200 °F
999.9 -99.9 999.9 °F