Specifications

General Features

Technical Reference

.
.
.
.

.
.
.

.
.

.

Dual channel closed loop control.

Temperature and relative humidii.
51 time-based steps for ramping.
8 event outputs per step.

1 event input.

1 remote hold input.
Data communications interface optional.

Fully programmable parameters.
Membrane faceplate.
User-friendly, 1/2 DIN plug in chassis.

Three year warranty.

Control Mode

l

Microprocessor-based user selectable modes.

l

Dual channel with dual control outputs per channel.

l

Control parameters user selectable.

Channels

1

& 2 as Temp & Temp

or

Temp

& RH.

On/Off switching hysteresis: 0.3°F or 0.3% RH with RTD or 0-5VDC inputs.
On/Off
switching hysteresis: 3.0°F for T/C.

PID parameters per channel or per output.
Proportional band: 0-500°F or 060% RH.

Reset: 0.00-20.00 repeats per minute.
Rate: 0.00-5.00 minutes.
Rate band: 0-3 times proportional band.

Cycle time: 0-60 seconds.

Deadband: +20° On/Off or ±20° with PID.

l

Alarm parameters user selectable.

l

Latching or non-latching, both channels.

l

Process high & low and deviation high & low per channel.

l

51 steps each selectable as:

l

Set point value.

l

Ramping, value and time.

l

Wait For, time or value

l

Jump/Loop to another step.

Operator Interface

l

Membrane front panel user-friendly I/2 DIN size.

l

Four digit 1/2” LED’s displaying actual process input value.

l

-Eight character alphanumeric 1/2” LED’s displaying set point, step number, and

various prompts and values for

1500.

l

Nineteen LED’s to indicate various status conditions.

l

Nine keys for control and value entry.

Input

.

Thermocouple, RTD, and electrical % RH input.

l

Automatic cold junction compensation for thermocouples.

l

RTD input 2 or 3 wire, platinum, 100ohms Ω @ 25°C, calibrated to curve #3916

(0.003916ohms/ohms/°CΩ Ω Ω Ω

DIN curve calibration ##3850 (0.003850ohms/ohms/°C available upon request.

l

Sensor break protection de-energizes output to protect system.

l

°F, °C or % RH is user selectable, RTD version.

80

WATLOW Series 1500 User's Manual

Specifications, Appendix