beautypg.com

Upper/lower set point limits, Alarm display codes, Alarm results – Watlow Electric Ramping and Profiling Microprocessor-Based Control SERIES 1500 User Manual

Page 50: Clearing alarms

background image

Technical Reference

Alarm Display Codes

h in the FUNCTION display, indicating the type of alarm. These alarm messages are
listed below. The first two are operational alarms that have no effect on alarm/event

outputs.

A0 - Low RAM back up battery A5 - Ch - 1 Lower deviation exceeded

NOTE: Al - Power intenupt A6 -- Ch - 2 Upper Process exceeded

A2

An Al power

- Ch - 1 Upper Process exceeded A7 - Ch -2 Lower Process exceeded

interrupt alarm

A3

-

Ch - 1 Lower Process exceeded

A8 - Ch

-

2 Upper deviation exceeded

A4

A9 -

will always flash

- Ch - 1

Upper

deviation exceeded

Ch - 2 Lower deviation exceeded

until an operator

presses the CLEAR

If more than one alarm condition is present, the lowest numbered alarm code will take

key (or sends

precedence. That is, if alarms Al and A6 are present, only Al will flash. If you clear

ALMOO), regardless

Al, then A6 will flash.

if aIarms are latched
or unlatched.

Alarm Results

What happens when

an alarm occurs depends on how you have the auxiliary output

(Event

#4) wired. The

alarms by themselves don’t stop the Series 1500 program or

shut down the outputs.

The only alarm that has an effect on the Series 1500 program is “Al” - power

interrupt. If your unit has a battery-backed real time clock, and a short power

interruption occurs, the 1500 will pick up the program where it left off. The program
however, will be running behind the real time clock (correct time) by the duration of

the power outage. A “Waitfor" time step in the program would correct that time lag in
the next 24 hour period.

If your 1500 does not have a battery-backed clock and a short power outage occurs,

the 1500 still picks up on the step it left off,

but

both the real time clock and the

program will be running behind by the duration of the power outage. A Waitfor time
step will not re-synchronize the program and correct real time in this case.

Clearing Alarms

To clear the power intenupt alarm (Al,

and

alarms with the “latch” option, press the

CLEAR key in the MNTR DATA mode.

If an alarm condition is no longer present, the alarm will remain cleared. If the

condition is still present, the alarm message will reappear. In that case, you must
correct the condition that caused the alarm before it will clear.

Upper and Lower Set Point Limits are Display and Scroll
Limits, Not Alarms

The upper and lower set point limits, U1/L1 and U2/L2, are not alarms. They are

configured to limit the range of display and the scrolling capability of the Series 1500.

It is possible to have alarm points beyond the upper and

lower limits of the control’s

set points.

50

WATLOW Series 1500 User's Manual

Alarms, Chapter 4