Performance data (5 ton), High efficiency – Trane RT-PRC005 User Manual
Page 38

38
RT-PRC005-EN
Performance
Data
(5 Ton)
High Efficiency
Table PD-42— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1)
1600
—
—
703
0.36
757
0.41
806
0.47
854
0.52
899
0.58
944
0.65
985
0.73
1023
0.79
1060
0.86
1800
706
0.42
760
0.47
815
0.54
861
0.60
904
0.66
947
0.72
988
0.78
1028
0.86
1067
0.94
1104
1.02
2000
773
0.57
821
0.62
873
0.69
918
0.76
958
0.83
998
0.90
1036
0.96
1073
1.02
1111
1.10
1147
1.19
2200
840
0.75
885
0.80
930
0.87
977
0.95
1016
1.03
1053
1.10
1089
1.17
1124
1.24
1158
1.31
1191
1.39
2400
909
0.96
950
1.02
990
1.08
1034
1.16
1074
1.25
1110
1.00
1143
1.42
1177
1.50
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.
Table PD-42 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1600
1093
0.92
1126
0.99
1160
1.06
1190
1.13
1222
1.20
1800
1138
1.10
1171
1.17
1203
1.25
1232
1.32
1262
1.39
2000
1182
1.28
1215
1.37
1246
1.46
—
—
—
—
2200
1226
1.48
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
—
—
PD-43 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1000
985
0.56
1021
0.62
1058
0.68
1093
0.74
1126
0.80
1200
1015
0.65
1051
0.71
1086
0.77
1120
0.84
1154
0.91
1400
1052
0.77
1088
0.84
1121
0.90
1153
0.97
1185
1.04
1600
1093
0.92
1126
0.99
1160
1.06
1190
1.13
1222
1.20
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008A Required.
2. BAYLSDR008A Required.
PD-43 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Downflow Airflow — Dehumidification (Hot Gas Reheat)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Low
Static Drive Accessory Kit (1)
1000
—
—
537
0.13
608
0.17
667
0.21
721
0.25
770
0.30
817
0.35
861
0.39
905
0.45
944
0.50
1200
517
0.15
588
0.19
652
0.23
712
0.28
764
0.33
811
0.38
856
0.43
898
0.48
939
0.54
978
0.59
1400
576
0.21
645
0.26
702
0.31
756
0.36
808
0.41
856
0.48
900
0.54
941
0.59
979
0.65
1017
0.71
1600
640
0.31
703
0.36
757
0.41
806
0.47
854
0.52
899
0.58
944
0.65
985
0.73
1023
0.79
1060
0.86
1-HP Standard Motor & Low
Static Drive Accessory Kit (2)
1-HP Standard
Motor & Drive