General data, General data (3 - 5 ton), Standard efficiency – Trane RT-PRC005 User Manual
Page 11

11
RT-PRC005-EN
General
Data
(3 - 5 Ton)
Standard Efficiency
Table GD - 1 — General Data
3 Ton Convertible Units
4 Ton Convertible Units
5 Ton Convertible Units
TSC036A1, A3, A4, AW
TSC048A1
TSC048A3, A4, AW
TSC060A1
TSC060A3, A4, AW
TSC060AK
Cooling Performance
1
Gross Cooling Capacity
37,400
50,300
49,200
63,100
63,100
63,100
SEER
2
10.7
5
10.1
10.0
9.9
10.2
10.2
Nominal CFM / ARI Rated CFM
1,200/1,200
1,600/1,600
1,600/1,600
2,000/2,000
2,000/2,000
2,000/2,000
ARI Net Cooling Capacity
36,000
48,000
47,000
60,000
60,000
60,000
System Power (kW)
3.91
8
5.28
5.40
6.86
6.78
6.78
Compressor
No./Type
1/Recip.
1/Scroll
1/Scroll
1/Scroll
1/Scroll
1/Scroll
Outdoor Sound Rating (dB)
3
83
86
82
84
84
84
Outdoor Coil — Type
Lanced
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size (in.) O.D.
0.3125
0.3125
0.3125
0.3125
0.3125
0.3125
Face Area (sq ft)
7.19
6.17
9.59
8.81
8.81
8.81
Rows/FPI
2/17
2/17
1/17
2/17
2/17
2/17
Indoor Coil — Type
Lanced
Lanced
Lanced
Lanced
Lanced
Lanced
Tube Size (in.)
0.3125
0.3125
0.3125
0.3125
0.3125
0.3125
Face Area (sq ft)
5.67
6.68
6.17
5.00
5.00
5.00
Rows/FPI
2/16
3/16
3/16
3/16
3/16
3/16
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Short Orifice
Drain Connection No./Size (in.)
1/¾ NPT
1/¾ NPT
1/¾ NPT
1/¾ NPT
1/¾ NPT
1/¾ NPT
Outdoor Fan — Type
Propeller
Propeller
Propeller
Propeller
Propeller
Propeller
No. Used/Diameter (in.)
1/22
1/22
1/22
1/22
1/22
1/22
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
Direct/1
Direct/1
Direct/1
CFM
2550
2850
3610
3470
3470
3470
No. Motors/HP
1/.20
1/.33
1/.33
1/.33
1/.33
1/.40
Motor RPM
1115
1115
1115
1115
1115
1115
Direct Drive Indoor Fan — Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used
1
1
1
1
1
1
Diameter x Width (in.)
10 x 10
11 x 11
11 x 11
11 x 11
11 x 11
12x11/–
Drive Type/No. Speeds
Direct/2
Direct/2
Direct/2
Direct/2
Direct/2
Direct/2
No. Motors
1
1
1
1
1
1
Motor HP (Standard/Oversized)
.33/.50
.60/.80
.60/.80
.90/1.00
.90/1.00
1.0/–
Motor RPM (Low/High Speed)
950/1060
930/1000
930/1000
985/1100
985/1100
935/1100
Oversized Motor RPM
(Low/High Speed)
1100/1145
1000/1100
1000/1100
1080/1135
1080/1135
—
Motor Frame Size
(Standard/Oversized)
48/48
48/48
48/48
48/48
48/48
48/—
Belt Drive Indoor Fan — Type
FC Centrifugal
—
FC Centrifugal
—
FC Centrifugal
—
No. Used
1
—
1
—
1
—
Diameter x Width (in.)
11 x 11
—
11 x 11
—
11 x 11
—
Drive Type/No. Speeds
Belt/Variable Speed
6
—
Belt/Variable Speed
—
Belt/Variable Speed
—
No. Motors
1
—
1
—
1
—
Motor HP
1.00
—
1.00
—
1.00
—
Motor RPM
1750
—
1750
—
1750
—
Motor Frame Size
56
—
56
—
56
—
Filters — Type Furnished
7
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
(No.) Size Recommended (in.)
(2) 20 x 25 x 1
(2) 20 x 25 x 1
(2) 20 x 25 x 1
(2) 20 x 25 x 1
(2) 20 x 25 x 1
(2) 20 x 25 x 1
Refrigerant Charge (Lbs of R-22)
4
3.8
4.4
3.8
4.7
4.9
4.9
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment
certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-51
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. TSC036A1 SEER is 10.5.
6. Belt Drive Motor is not available for TSC036A1.
7. Optional 2” Pleated Filters also available.
8. TSC036A1 System Power (kW) is 3.79.