General data (3 - 5 ton), High efficiency – Trane RT-PRC005 User Manual
Page 13

13
RT-PRC005-EN
General
Data
(3 - 5 Ton)
High Efficiency
Table GD - 3 — General Data
3 Ton
4 Ton
5 Ton
Convertible Units
Convertible Units
Convertible Units
THC036A1,A3,A4,AW
THC048A1,A3,A4,AW
THC060A1
THC060A3,A4,AW
Cooling Performance
1
Gross Cooling Capacity
38,000
49,800
62,100
62,400
SEER
/ EER
2
12.5/—
12.0/—
11.8/—
12.0/ —
Nominal CFM / ARI Rated CFM
1,200/1,200
1,600/1,600
2,000/2,000
2,000/2,000
ARI Net Cooling Capacity
36,600
47,500
59,000
59,500
System Power (kW)
3.33
4.48
5.73
5.56
Compressor
No./Type
1/Climatuff Scroll
1/Climatuff Scroll
1/Climatuff Scroll
1/Climatuff Scroll
Outdoor Sound Rating (dB)
3
83
85
84
84
Outdoor Coil — Type
Lanced
Lanced
Lanced
Lanced
Tube Size (in.) O.D.
0.3125
0.3125
0.3125
0.3125
Face Area (sq ft)
7.19
9.59
10.96
10.96
Rows/FPI
2/17
3/17
3/17
3/17
Indoor Coil — Type
Lanced
Lanced
Lanced
Lanced
Tube Size (in.)
0.3125
0.3125
0.3125
0.3125
Face Area (sq ft)
6.68
6.68
7.71
7.71
Rows/FPI
3/16
4/16
4/16
4/16
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Short Orifice
9
Drain Connection No./Size (in.)
1/¾ NPT
1/¾ NPT
1/¾ NPT
1/¾ NPT
Outdoor Fan — Type
Propeller
Propeller
Propeller
Propeller
No. Used/Diameter (in.)
1/22
1/22
1/22
1/22
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
Direct/1
10
CFM
2550
3050
3170
3370
No. Motors/HP
1/.20
1/.33
1/.33
1/.33
Motor RPM
1115
1115
1115
1115
Direct Drive Indoor Fan — Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used
1
1
1
1
Diameter x Width (in.)
10 x 10
11 x 11
11 x 11
11 x 11
Drive Type/No. Speeds
Direct/2
Direct/2
Direct/2
Direct/2
No. Motors
1
1
1
1
Motor HP (Standard/Oversized)
.33/.50
.60/.80
.90/1.00
.90/1.00
Standard Motor RPM (Low/High Speed)
950/1060
930/1000
985/1100
985/1100
Oversized Motor RPM (Low/High Speed)
1100/1145
1000/1100
1080/1135
1080/1135
Motor Frame Size (Standard/Oversized)
48/48
48/48
48/48
48/48
Belt Drive Indoor Fan — Type
FC Centrifugal
FC Centrifugal
—
FC Centrifugal
No. Used
1
1
—
1
Diameter x Width (in.)
11 x 11
11 x 11
—
11 x 11
Drive Type/No. Speeds
Belt/Variable Speed
6
Belt/Variable Speed
6
—
Belt/Variable Speed
No. Motors
1
1
—
1
Motor HP
1.00
1.00
—
1.00
Standard Motor RPM
1750
1750
—
1750
Motor Frame Size
56
56
—
56
Filters — Type Furnished
7
Throwaway
Throwaway
Throwaway
Throwaway
(No.) Size Recommended (in.)
(2) 20 x 25 x 1
(2) 20 x 25 x 1
(2) 20 x 30 x 1
(2) 20 x 30 x 1
11
Optional Hot Gas Reheat Coil - Type
—
—
—
Lanced
Tube Size (in.) OD
—
—
—
0.375
Face Area (sq. ft)
—
—
—
2.22
Rows/FPI
—
—
—
2/18
Refrigerant Charge (Lbs of R-22)
4
Standard
5.3
8
7.7
5
7.9
8.4
Optional Hot Gas Reheat Coil
—
—
—
10.7
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner
Equipment certification program, which is based on ARI Standard 210/240.
2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-51
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 8.1.
6. Belt Drive Motor is not available for THC036A1, THC048A1.
7. Optional 2” Pleated Filters also available.
8. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 4.5.
9. TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.
10. With Dehumidification (Hot Gas Reheat) option: Direct/2.
11. 2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.