Electrical data – Trane RT-DS-10 User Manual

Page 31

background image

31

Electrical

Data

Table 31-1 – Electrical Service Sizing Data

Fan Motors

Compressor

Supply

Condenser

Electrical

2

Qty./

RLA

LRA

FLA

Max.

Model

Characteristics

Nominal HP

(Ea.)

Ea.)

HP

FLA

No.

HP

(Ea.)

MCA*

Fuse Size

TC/TE/YC*275

380-415/50/3

2/10,15

18.1/27.3

110/174

5

13.1

3

.75

4.4

 79

100

TC/TE/YC*305

380-415/50/3

2/15,15

27.3

174

5

13.1

3

.75

4.4

 93

110

TC/TE/YC*350

380-415/50/3

2/15,15

27.3

174

5

13.1

3

.75

4.4

 93

110

TC/TE/YC*400

380-415/50/3

2/15,15

27.3

174

7.5

16.6

4

.75

4.4

119

125

1/10

18.1

110

TC/TE/YC*500

380-415/50/3

3/15

27.3

174

7.5

16.6

4

.75

4.4

128

150

Notes:

1. All customer wiring and devices must be installed in accordance with local and national electrical codes.

2. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.

* Minimum Circuit Ampacity.

Table 31-2 – Electrical Service Sizing Data – Electric Heat Module

(Electric Heat Units Only)

Models: TED/TEH 275 thru 500

Electric Heat FLA

Nominal

Nominal

Unit Size

Unit

KW Heater (380/415V)

(Tons)

Voltage

23/27

34/40

45/54

56/67

68/81

23-29

380

34.5

51.1

68.9

85.5

–

415

37.6

55.6

–

–

–

33, 43

380

–

51.1

68.9

85.5

103.4

415

–

55.6

75.1

93.2

112.7

Notes:

1. All FLA in this table are based on heater operating at 380 or 415 volts as shown above.