Electrical data – Trane RT-DS-10 User Manual
Page 31
31
Electrical
Data
Table 31-1 Electrical Service Sizing Data
Fan Motors
Compressor
Supply
Condenser
Electrical
2
Qty./
RLA
LRA
FLA
Max.
Model
Characteristics
Nominal HP
(Ea.)
Ea.)
HP
FLA
No.
HP
(Ea.)
MCA*
Fuse Size
TC/TE/YC*275
380-415/50/3
2/10,15
18.1/27.3
110/174
5
13.1
3
.75
4.4
79
100
TC/TE/YC*305
380-415/50/3
2/15,15
27.3
174
5
13.1
3
.75
4.4
93
110
TC/TE/YC*350
380-415/50/3
2/15,15
27.3
174
5
13.1
3
.75
4.4
93
110
TC/TE/YC*400
380-415/50/3
2/15,15
27.3
174
7.5
16.6
4
.75
4.4
119
125
1/10
18.1
110
TC/TE/YC*500
380-415/50/3
3/15
27.3
174
7.5
16.6
4
.75
4.4
128
150
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
* Minimum Circuit Ampacity.
Table 31-2 Electrical Service Sizing Data Electric Heat Module
(Electric Heat Units Only)
Models: TED/TEH 275 thru 500
Electric Heat FLA
Nominal
Nominal
Unit Size
Unit
KW Heater (380/415V)
(Tons)
Voltage
23/27
34/40
45/54
56/67
68/81
23-29
380
34.5
51.1
68.9
85.5
415
37.6
55.6
33, 43
380
51.1
68.9
85.5
103.4
415
55.6
75.1
93.2
112.7
Notes:
1. All FLA in this table are based on heater operating at 380 or 415 volts as shown above.