beautypg.com

Selection procedure – Trane RT-DS-10 User Manual

Page 15

background image

15

Selection

Procedure

Selection of Trane commercial air

conditioners is divided into five basic

areas:

1

Cooling capacity

2

Heating capacity

3

Air delivery

4

Unit electrical requirements

5

Unit designation
Factors Used In Unit Cooling Selection:

1

Summer design conditions – 95 DB/

76 WB (35/24.4°C), 95°F (35°C) entering

air to condenser.

2

Summer room design conditions –

76 DB/66 WB (24.4/18.9°C).

3

Total peak cooling load – 270 MBh

(79 kW) (22.5 tons).

4

Total peak supply cfm – 10,000 cfm

(4720 l/s).

5

External static pressure – 1.0 inches wc

(249 Pa).

6

Return air temperatures – 80 DB/66°F

WB (26.7/18.9°C).

7

Return air cfm – 3540 cfm (1671 l/s).

8

Outside air ventilation cfm and load –

1000 cfm and 15.19 MBh (1.27 tons or

4.45 kW) 472 l/s.

9

Unit accessories include:

a

Aluminized heat exchanger – high heat

module.

b

2” Hi-efficiency throwaway filters.

c

Exhaust fan.

d

Economizer cycle.

Step 1 – A summation of the peak

cooling load and the outside air

ventilation load shows: 22.5 tons + 1.27

tons = 23.77 (79 kW + 4.45 kW = 83.45)

required unit capacity. From Table 19-1,

25 ton (89 kW) unit capacity at 80 DB/67

WB (27/19°C), 95°F entering the

condenser and 10,000 total peak supply

cfm (4720 l/s), is YC/TC/TE*305.
Step 2 – Having selected the correct

unit, the supply fan and exhaust fan

motor bhp must be determined.
Supply Air Fan:

Determine unit static pressure at

design supply cfm:

External static pressure

1.25 inches

(310 Pa)

Heat exchanger

  (Table 28-1)

.12 inches

(30 Pa)

High efficiency filter 2” (25 mm)

  (Table 28-1)

.07 inches

(17 Pa)

Economizer

  (Table 28-1)

.07 inches

(17 Pa)

Unit total static pressure

1.50 inches

(374 Pa)

Using total cfm of 10,000 (4720 l/s) and

total static pressure of 1.50 inches

(38 mm), enter Table 24-1. Table 24-1

shows 5.35 bhp (4 kW) with 616 rpm.
Step 3 – Determine evaporator coil

entering air conditions. Mixed air dry

bulb temperature determination.
Using the minimum percent of OA

(1,000 cfm ÷ 10,000 cfm = 10 percent),

determine the mixture dry bulb to the

evaporator. RADB + % OA

(OADB - RADB) = 80 + (0.10) (95 - 80) =

80 + 1.5 = 81.5°F [26.7 + 1.5 = 28°C).
Approximate wet bulb mixture

temperature:
RAWB + OA (OAWB - RAWB) =

66 + (0.10) (76-66) = 68 + 1 = 67°F.
A psychrometric chart can be used to

more accurately determine the mixture

temperature to the evaporator coil.

Step 4 – Determine total required unit

cooling capacity:

Required capacity = total peak load +

O.A. load + supply air fan motor heat.
From Figure 16-1, the supply air fan

motor heat for 5.85 bhp = 15 MBh.
Capacity = 270 + 15 + 15 =

300 MBh (89 kW)
Step 5 – Determine unit capacity:

From Table 19-2 unit capacity at 81.5

DB/67 WB entering the evaporator,

10,000 supply air cfm, 95°F (35°C)

entering the condenser about 305.6

MBh (89.5 kW) with 241 MBh (70.6 kW)

sensible.
Step 6 – Determine leaving air

temperature:

Unit sensible heat capacity, corrected

for supply air fan motor heat 241 - 15 =

226 MBh (66.2 kW).
Supply air dry bulb temperature

difference = 226 MBh ÷ (1.085 x

10,000 cfm) = 20.8°F (-6.2°C)
Supply air dry bulb: 81.5-20.8 = 60.7

(15.9°C)
Unit enthalpy difference = 305.6 ÷

(4.5 x 10,000) = 6.79

Btu/lb leaving enthalpy = h (ent WB)

= 31.62

Leaving enthalpy = 31.62 Btu/lb -

6.79 Btu/lb = 24.83 Btu/lb.
From Table 17-1, the leaving air wet

bulb temperature corresponding to an

enthalpy of 24.8 Btu/lb = 57.5.

Leaving air temperatures = 61.7 DB/

57.5 WB (15.9/13.9°C).