General data – Trane RT-DS-10 User Manual
Page 12
12
General
Data
Table 12-1 General Data 43 Tons
TC*500 (42Tons)
Cooling Performance
1
Nominal Gross Capacity(Btuh)
505,000 (148 kW)
System Power kW
52.9
Compressor
Number/Type
3/Scroll
Nominal Motor HP (ea)
12.5
Motor RPM
2875
Natural Gas Heat
2
Low
High
Heating Input(Btuh)
335,000 (98.2 kW)
670,000 (196 kW)
First Stage
300,000 (87.9 kW)
600,000 (176 kW)
Heating Output(Btuh)
271,350 (79.5 kW)
542,700 (159 kW)
First Stage
243,500 (71.4 kW)
486,000 (166 kW)
Steady State Efficiency(%)
3
81
No. Burners/No. Stages
1/2
Gas Connect Pipe Size (in)
0.75 (19 mm)
Outdoor Coil - Type
LANCED
Tube Size OD (in)
0.375 (10 mm)
Face Area(sq ft)
69.8 (6.5 sq m)
Rows/Fins Per Inch (25mm)
2/16
Indoor Coil - Type
HI-PERFORM
Tube Size OD (in)
0.500 (13 mm)
Face Area (sq ft)
37.5 (3.5 sq m)
Rows/Fins Per Inch (25mm)
3/13
Refrigerant Control
TXV
PVC Drain Connect No./Size (in)
1/1.25 (1/32 mm)
Outdoor Fan Type
PROP FAN
No. Used
4
Diameter (in.)
28.0 (711 mm)
Drive Type/No. Speeds
DIRECT/1
Cfm
26,200 (12,400 L/s)
No. Motors (RPM)
4 (940)
Motor HP
0.75 (0.56 kW)
Indoor Fan Type/No. Used
FC/1
Diameter (in)
25.0 (635 mm)
Width (in)
25.0 (635 mm)
Drive Type
BELT
No. Speeds/No. Motors
1/1
Motor HP
10.0 (7.5 kW)
Motor RPM/Frame Size
1460/215T
Filters - Type
THROWAWAY
Furnished/No.
Yes/17
Recommended Size (in)
16x20x2 (406x508x51mm)
Refrigerant Type
R-22
Factory Charge Circuit #1 (lbs)
4
23.9 (10.8 kg)
Factory Charge Circuit #1
49.4 (22.5 kg )
Notes:
1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (27°C) entering dry bulb, 67°F (19°C) entering
wet bulb. Gross capacity does not include the effect of fan motor heat.
2. Heating Performance Limit settings and ratings data were established and approved under laboratory
test conditions using American National Standards.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service
instructions.
Table 12-2 Economizer Outdoor Air Damper Leakage (Of Rated Airflow)
∆
P Across Dampers (In. WC) (Pa)
0.5 In. (124.5 Pa)
1.0 In. (249 Pa)
Standard
1.5%
2.5%
Optional Low Leak
0.5%
1.0%
Note: Above data based on tests completed in accordance with AMCA Standard 575.