12

General

Data

Table 12-1 – General Data – 43 Tons

TC*500 (42Tons)

Cooling Performance

1

  Nominal Gross Capacity(Btuh)

505,000 (148 kW)

  System Power kW

52.9

Compressor

  Number/Type

3/Scroll

  Nominal Motor HP (ea)

12.5

  Motor RPM

2875

Natural Gas Heat

2

Low

High

  Heating Input(Btuh)

335,000 (98.2 kW)

670,000 (196 kW)

  First Stage

300,000 (87.9 kW)

600,000 (176 kW)

  Heating Output(Btuh)

271,350 (79.5 kW)

542,700 (159 kW)

  First Stage

243,500 (71.4 kW)

486,000 (166 kW)

  Steady State Efficiency(%)

3

81

  No. Burners/No. Stages

1/2

  Gas Connect Pipe Size (in)

0.75 (19 mm)

Outdoor Coil - Type

LANCED

  Tube Size OD (in)

0.375 (10 mm)

  Face Area(sq ft)

69.8 (6.5 sq m)

  Rows/Fins Per Inch (25mm)

2/16

Indoor Coil - Type

HI-PERFORM

  Tube Size OD (in)

0.500 (13 mm)

  Face Area (sq ft)

37.5 (3.5 sq m)

  Rows/Fins Per Inch (25mm)

3/13

  Refrigerant Control

TXV

  PVC Drain Connect No./Size (in)

1/1.25 (1/32 mm)

Outdoor Fan Type

PROP FAN

  No. Used

4

  Diameter (in.)

28.0 (711 mm)

  Drive Type/No. Speeds

DIRECT/1

  Cfm

26,200 (12,400 L/s)

  No. Motors (RPM)

4 (940)

  Motor HP

0.75 (0.56 kW)

Indoor Fan Type/No. Used

FC/1

  Diameter (in)

25.0 (635 mm)

  Width (in)

25.0 (635 mm)

  Drive Type

BELT

  No. Speeds/No. Motors

1/1

  Motor HP

10.0 (7.5 kW)

  Motor RPM/Frame Size

1460/215T

Filters - Type

THROWAWAY

  Furnished/No.

Yes/17

  Recommended Size (in)

16x20x2 (406x508x51mm)

Refrigerant Type

R-22

  Factory Charge Circuit #1 (lbs)

4

23.9 (10.8 kg)

  Factory Charge Circuit #1

49.4 (22.5 kg )

Notes:

1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (27°C) entering dry bulb, 67°F (19°C) entering

wet bulb. Gross capacity does not include the effect of fan motor heat.

2. Heating Performance Limit settings and ratings data were established and approved under laboratory

test conditions using American National Standards.

3. Steady State Efficiency is rated in accordance with DOE test procedures.

4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service

instructions.

Table 12-2 – Economizer Outdoor Air Damper Leakage (Of Rated Airflow)

P Across Dampers (In. WC) (Pa)

0.5 In. (124.5 Pa)

1.0 In. (249 Pa)

  Standard

1.5%

2.5%

  Optional “Low Leak”

0.5%

1.0%

Note: Above data based on tests completed in accordance with AMCA Standard 575.