MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-42

24 March 2006

Issue 1.5

3.20.3 DIM800

DETECTOR

COMPATIBILITY

Series

Model

Max Qty External Supply

Voltage at DIM

614P Photo Detector

25

20.0V – 28.7V

614I Ionisation Detector

38

20.0V – 28.7V

614CH Carbon Monoxide + Heat Detector

32

20.0V – 28.7V

614T Heat Type A, B, C, D

23

20.7 – 28.7V

MD614 Heat Detector

40

20.7V - 28.7V

MR614 Photo Detector

22

20.7V - 28.7V

MR614T HPO Detector

21

20.7V - 28.7V

MU614 CO Detector

40

20.7V - 28.7V

MF614 Ionisation Detector

30

20.7V - 28.7V






Minerva

T614 Heat Type A, B, C, D

23

20.7V - 28.7V

4098 – 9603EA Ionisation Detector

24

20.0V - 28.7V

4098 – 9601EA Photo Detector

24

20.0V - 28.7V



Simplex

4098 – 9618EA,-9619EA,-9621EA Heat
Detectors

24

20.0V - 28.7V

P24B Photoelectric Detector

24

20.7V - 24.7V

P29B Photoelectric Detector

20

20.7V - 26.7V

C24B Ionisation Detector

40

20.7V - 26.7V

C29B (Ex) Ionisation Detector

40

20.7V - 26.7V

R23B Flame Detector*

20

20.7V - 24.7V

R24B Flame Detector

3

22.7V - 28.7V

DO1101 Photo Detector*

16

21.7V - 27.7V

DLO1191 Beam Detector*

1

22.7V - 28.7V

P136 Duct Sampling Unit

5

20.0V - 28.7V

T56B Heat Detector

40

20.0V - 28.7V

All above Olsen Detectors with Z52B, Z54B,
Z54B Mk2, Z56, Z500 base as appropriate








Olsen

T56B Heat Detector with
Z52B, Z55B, Z56N, Z500N Base

40

20.0V - 28.7V

System
Sensor

885WP-B Weatherproof Heat Detector
Type B *@

40

20.0V – 28.7V

-

Hard Contact Devices (T54B, B111, etc)

40

20.0V - 28.7V

Hard contact devices must be rated for at least 30V and currents up to 50mA.
*

Not an SSL Listed combination

@

Remote indicator output cannot be used in common with Tyco 614 series or the

Minerva M614 series (and most other Tyco/Olsen) detectors.

Table 3-4 Conventional Detector Compatibility

3.20.4

MX4428 PROGRAMMING OPTIONS - DIM800

Parameter Description

Default

Value Description
0

Short = Alarm

Mode

1

Short = Fault

0

P1

Normal to Alarm Threshold

51

P2

Normal to Fault Threshold

22

P3

Supply Fault Threshold

60 (this is MXP default used if
MX4428 value = 0).
On the latest revision of
DIM800, the threshold cannot
be usefully varied by changing
this parameter.

P4

Alarm to Short Threshold

225 (this is MXP default used
if MX4428 value = 0)