beautypg.com

Tyco MX4428 User Manual

Page 38

background image

MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-22

24 March 2006

Issue 1.5

The following global parameters which may be set at the MX4428 affect all applicable points
on all MXPs.

MX4428 Reference

Description

Default

8XXPH UPPER
TRACKING LIMIT

Photo Upper Tracking Limit (i.e. the
maximum assumed value for clean
air)

56 (MXP Default)

8XXPH DIRTY
ALERT LIMIT

Photo Dirty Alert Limit (i.e. a “dirty
alert” will be raised if the tracked
“clean air” value reaches this limit)

56

8XXPH TRACK
INTERVAL

Photo Tracking Interval
i.e. the interval at which the tracked
“clean air” value is adjusted.

30 (minutes)

8XXPH FUZZY
ALGORITHM

Fuzzy Sensitivity if Device Parameter
1 is not 0, 1, or 2
0 = low
1 = medium
2 = high

1 (medium)
(MXP also chooses
Medium if this
parameter is not 0,
1, or 2)