MX4428 MXP Engineering / Technical Manual

Document: LT0273

MXP Loop Filter Board

Page 9-14

24 March 2006

Issue 1.5


Both short circuit faults and open circuit faults will be logged as SUPERVISION FAULT, and
relay stuck faults will be logged as CONTROL CB FAIL. Only the first fault will be logged.
When all relay faults go away, the event logged at the MX4428 will be NORMAL OFF or
NORMAL ON as the case may be, regardless of the original fault logged.

9.11

LPS PROCESSING

9.11.1

ELD AND POSITION MONITORING

Correct Relay Position

AI0, AI1

Condition

AI0 > 200 AND AI1 < 50

Open circuit fault

50 < AI0 <= 110

Short circuit

0 <= AI0 <=50

Relay fault

Not activated

Otherwise Normal

AI0 > 50

Relay Fault

AI0 <= 50 AND AI1 <= 50

Short circuit

AI0 <= 50 AND 50 < AI1 <= 200

Relay Fault

Activated

Otherwise Normal


Changes in these states are verified as described in section 9.22.

Both short circuit faults and open circuit faults will be logged as SUPERVISION FAULT, and
relay stuck faults will be logged as CONTROL CB FAIL. Only the first fault will be logged.
When all relay faults go away, the event logged at the MX4428 will be NORMAL OFF or
NORMAL ON as the case may be, regardless of the original fault logged.

9.12

VLC800

PROCESSING

9.12.1 GENERAL

The VLC800 is processed like an 814PH, with the following parameters.
Tracked Value is fixed at 12.
Alarm Threshold is fixed at 100. (Corresponding to a raw value of 112).
Filter Divisor is fixed at 3.
Step Limit is 255 (so essentially there is no step limit).
PreAlarm is adjustable at the MX4428.

So the only filtering is the exponential filter with a filter divisor of 3. This gives some filtering,
but with a minimal delay.

As the alarm threshold is always 100, the current level (CV-TV) is an indication of the smoke
level in terms of % of the alarm threshold programmed into the VLC800 itself.