MX4428 MXP Engineering / Technical Manual

Document: LT0273

Device Information and Programming

Page 3-18

24 March 2006

Issue 1.5

Parameter Description

Default

Value

Functional Base Control

Remote LED Control

0

Circuit Alarm

Circuit Alarm

1 Circuit

Alarm

Relay

2

Circuit Alarm

Point Alarm

4 Relay

Circuit

Alarm

5 Relay

Relay

6 Relay

Point

Alarm

8

Point Alarm

Circuit Alarm

9 Point

Alarm

Relay

Mode

10

Point Alarm

Point Alarm

0

P0

Pre Alarm Threshold

50

Alarm Threshold
Value Threshold
23

0.22 MICX (Alternate)

66 0.39

MICX (Default)

P1

130 0.59

MICX

66

P2

Fault Limit (i.e. values below this are assumed to indicate a
detector fault)

10

P3

Dirty Alert Limit (i.e. a “dirty alert” will be raised if the
tracked “clean air” value reaches this limit)

120

b3:b0

Filter Divisor

3

P4

b7:b4

Step Limit

5

P5

Tracking Interval i.e. the interval at which the tracked “clean
air” value is adjusted.

30 (minutes)

P6

Tracking adjustment - fixed at 1 in MXP

1


The following global parameters which may be set at the MX4428 affect all applicable points
on all MXPs.

MX4428 Reference

Description

Default

8XXI UPPER
TRACKING LIMIT

Ionisation Upper Tracking Limit
(i.e. the maximum assumed value for
clean air)

120 (MXP
Default)