MX4428 MXP Engineering / Technical Manual

Document: LT0273

MXP Loop Filter Board

Page 9-12

24 March 2006

Issue 1.5

9.8

DIM

PROCESSING

9.8.1 LOAD

GRAPH

Figure 9.8 shows the V / I characteristics for the DIM detector terminals, together with the
fault and alarm thresholds when using the default parameters. The shaded areas show the
region of uncertainty.

Three lines are shown for three supply voltages.

0

5

10

15

20

25

30

0

10

20

30

40

50

Load Current (mA)

Loa

d

V

o

lta

ge

28V

24V

19V

4k7 EOL

A

L

A

R

M

N

O

R

M

A

L

F

A

U

L

T

Figure 9.8 DIM LoadLine Characteristics

9.8.2 DIM

MODEL

The reading from the DIM module can be modelled using the following method.
Calculate “R” from a point on the load line = Load Voltage / Load Current.
Reading = 137000 / (560 + R)

For example take the point where the 4k7 EOL resistor crosses the 24V line.
R

= 20.8 / .0044

=

4700

Reading

= 137000 / (560 + 4700)

=

26

Note that for a given “R”, the reading is independent of the supply voltage.

9.8.3

ALGORITHM - DIM800

The unverified input condition is evaluated according to the following table, depending on the
values of parameters P1, P2, and P4. (if P4 is 0, assume it is 225).

Input

Condition (Mode 0)

Condition (Mode 1)

P4 <= reading <= 255

Alarm

Short

P1 <= reading < P4

Alarm

Alarm

P2 <= reading < P1

Normal

Normal

0 <= reading < P2

Open circuit fault

Open circuit fault


Changes in these states are verified as described in section 9.22.