MX4428 MXP Engineering / Technical Manual

Document: LT0273

MXP Loop Filter Board

Page 9-8

24 March 2006

Issue 1.5

9.5

CO

PROCESSING

9.5.1 CALIBRATION

AND

TEMPERATURE COMPENSATION

The CO reading of the detector is returned as input AI0 of the device ASIC. The CO
readings are adjusted depending on a calibration factor set at the factory and stored in
EEPROM.

9.5.2

“ENHANCEMENT”

Figure 9.3 shows the amount by which CO readings are increased depending on the
temperature rate of rise. (This is the same for the CO detector as the Photo detector.)

The default enhancement multiplier parameter is 12. The graph (Figure 9.3) shows the effect
of this factor and also the effect of an alternative parameter of 6.

If enhancement is disabled, (or less efficiently if the enhancement multiplier parameter is set
to 0) the multiplier is exactly 1.

9.5.3 CO

PROCESSING

Subtractor

+

-

Calibration

Adder

Exponential
Filter

Subtractor

Enhancement Factor
derived from Heat RORCV
(1 if no enhancement)

Adder

Multiplier

Slope
Limiter

TV = Tracked Value = Zero CO Value

Raw
Value

-

+

+

+

+

+

-

-

-

-

Alarm Threshold

Alarm

Subtractor

Subtractor

Comparator

Comparator

PreAlarm Threshold

PreAlarm

CVEnh
(CV to FIP)

SLV

Constant stored
in detector eeprom

CO Filter
Divisor

CO Step Limit

Figure 9.5 CO Processing Diagram