Document: LT0273

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Issue 1.5

24 March 2006

Page 3-7

3.2

DEVICE HANDLING CAPABILITY

3.2.1 OVERVIEW

The parameters which determine the maximum number of each device type that can be put
on a loop are as follows. The column “MAX NO. DEVICES” assumes that all devices are of
the same type. If this is not the case, it is necessary to perform the calculations described
below.

DEVICE MAX

NO.

DEVICES

Quiescent

Current

Alarm

Current

AC Units

(max 250

total)

IB Units

(max 100 IB

units between

Isolator Bases)

814I 200

330uA

3.0mA

1

1.4

814H 200

250uA

3.0mA

1

1

814PH 200

275uA

3.0mA

1

1.2

814P 200

275uA

3.0mA

1

1.2

814CH 200

275uA

3.0mA

1

1

MIM800

200

275uA

2.8mA (with LED)
275uA (no LED)

1 1.5

MIM801

200

275uA

2.8mA (with LED)
275uA (no LED)

1 1.5

CIM800 200

275uA

2.8mA

1

1

DIM800 200

100uA
(Loop)

100uA (Loop)

1

1

CP820 200

275uA

2.8mA

1

1.5

RIM800

200

285uA

2.8mA (with LED)
285uA (no LED)

1 5

SNM800

200

450uA

3.0mA (with LED)
450uA (no LED)

1 5

LPS800

33 or less,

depends on

load

450uA Load

current

+

4mA, with
minimum of 12mA

1.5 1

5BI N/A

80uA

0.2 N/A

814SB 40(Quiet)

30(Medium)
24(Loud)

400uA 9mA(Quiet)

12mA(Medium)
15mA(Loud)

2.4 2.5

802SB* 200(Quiet)

50 (Loud)

200uA 1.2mA

(Quiet)

6.8mA (Loud)

0.5 2.5

812SB* 18

200uA

21mA

0.5

2.5

901SB* 200

200uA

200uA

(Loop) 0.5

2.5

912SB* 200

200uA

200uA(

Loop) 0.5

2.5

814RB 200

50uA

100uA

0.3

1.6

VLC800

125

300uA

300uA (no LED)
2.8mA (with LED)

2 1

*Models of MkII Sounder Base

Table 3-2 Device Quantities and Loading


The particular combination of device types, external loads, cable length and type may limit
the total number of devices. This is calculated in the following sections.

There are two types of load which must be considered - DC and AC. Also if isolator bases
are used, the loading between each isolator base must be considered.