Tyco 1540 User Manual
Page 61

59
Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03
Modbus Holding Registers and Integra set up
Holding registers are used to store and display instrument configuration settings. All holding
registers not listed in the table below should be considered as reserved for manufacturer use
and no attempt should be made to modify their values.
The demand parameters may be viewed or changed using the Modbus protocol. Each parameter
is held in the 4X registers. Modbus Function Code 03 is used to read the parameter and Function
Code 16 is used to write.
Password Settings marked r/wp require the instrument password to have been entered into the
Password register before changes will be accepted. Once the instrument configuration has been
modified, the password should be written to the password register again to protect the
configuration from unauthorised or accidental change. Power cycling also restores protection.
Reading the Password register returns 1 if the instrument is unprotected and 0 if it is protected
from changes.
Demand Time is used to reset the demand period. A value of zero must be written to this
register to accomplish this. Writing any other value will cause an error to be returned. Reading
this register after instrument restart or resetting demand period gives the number of minutes of
demand data up to a maximum of the demand period setting. For example, with 15 minute
demand period, from reset the value will increment from zero every minute until it reaches 15.
It will remain at this value until a subsequent reset occurs.
Demand Period The value written must be one of the following 8,15, 20 or 30 (minutes),
otherwise an error will be returned.
System Type The System type address will display '1' for single phase 2 wire, '2' for 3 Phase 3
Wire, '3' for 3 Phase 4 Wire or 4 for single phase 3 wire.
Register
Parameter
Parameter
Modbus Start
Valid range
Mode
Number
Address Hex
High
Low
Byte
Byte
40001
1
Demand Time
00
00
0 only
r/w
40003
2
Demand Period
00
02
8,15,20,30 minutes.
r/w
40007
4
System Voltage
00
06
1V - 400kV
r/wp
40009
5
System Current
00
08
1-9999 A
r/wp
40011
6
System Type
00
0A
ro
40013
7
Relay Pulse Width
00
0C
3,5,10 (x20mS)
r/w
40015
8
Energy Reset
00
0E
0 only
wo
40023
12
Pulse Divisor
00
16
1,10,100,1000
r/w
40025
13
Password
00
18
0000-9999
r/w
40037
19
System Power
00
24
r/o
40041
21
Register Order
00
28
2141.0 only
wo
40299
150
Secondary Volts
01
2A
Min Vin-Max Vin
r/wp
r/w = read/write r/wp = read and write with password clearance ro = read only wo = write only