4.3.6 Nominal range of use of influence quantities for measurands
Values of quantities which affect measurement errors to a minor degree for which the
magnitude of the measurement error is defined in this specification.
Voltage
50 .. 120% of nominal
Current
5 .. 120% of nominal
Frequency
Nominal ±10%
Power factor (active/reactive
0.5 lagging .. 1 .. 0.8 leading ,importing
as appropriate)
Temperature
-20°C to +70°C
Input waveform distortion
20% 3rd Harmonic distortion
Auxiliary supply voltage
Nominal ±10%
Auxiliary supply frequency
Nominal ±10%
Magnetic field of external origin
400A/m
Crest values of voltage and current must remain within
168% of nominal maximum rms values
4.3.7 Functional ranges
The functional ranges of measurands and of influence quantities for measurands
Values of measured quantities, components of measured quantities, and quantities which affect
measurement errors to a minor degree, for which the product gives meaningful readings.
Voltage
5 .. 120% of nominal (below 5% of nominal voltage,
current indication is only approximate)
Current
0 .. 120% of nominal
(2 .. 120% of nominal for Power Factor)
Frequency
45 .. 66 Hz
Power Factor
1 .. 0 leading or lagging, importing (active/reactive as
appropriate)
Temperature
-20°C to +70°C
Active power (Watt)
0 .. 120% of nominal, 360 MW Max.
Reactive power (VAr)
0 .. 120% of nominal, 360 MVAr Max.
Apparent power (VA)
0 .. 120% of nominal, 360 MVA Max.
4.3.8 Screen
Update
0.5 second approx.
4.3.9 Standards
Terms, Definitions and Test Methods
IEC688 (BSEN 60688)
IEC1036 (BSEN 61036)
EMC IEC
61326
51